6.11.2.3. Configuring the Response
Next select the “Response” element from the Modbus command.
The various elements of the configuration of the response for this
command are shown opposite. The values displayed correspond to
the default values for any new command.
These elements allow you to configure a single aspect of managing the command, described at the top of the
page on the right. Each of these elements is described, in order, in the table below.
Configuration
element
Trigger byte
Trigger byte
address
Description
This element is used by the gateway to activate the unitary incrementation of an 8-bit
counter in order to notify the DeviceNet master of the receipt of a new response to the
associated Modbus command. It takes one of the following two values:
- Disabled.................................. Default configuration. The gateway does not increment any
counter on receipt of the Modbus response.
- Enabled .................................. Each time that the gateway receives a new response to the
associated Modbus command, it increments the value of an 8-bit counter designated
by the “Trigger byte address” element (see below). This change in the value of the
Trigger Byte Address can be used to notify the DeviceNet master that Modbus
Response data is ready to be polled.
This element is only used by the gateway if the element “Trigger byte” is set to “Enabled”. In
this case, it specifies the address, in the gateway’s input memory (0x0002 to 0x01FF), of an
8-bit counter managed by the gateway.
When the gateway receives a response to the associated Modbus command, it increments
the value of this counter in a unitary manner (value = value+1). So the DeviceNet master
must have access to this counter in the same way as for the periodic input registers from
the TeSys U motor starters.
This mode allows the DeviceNet master to be informed that a new response is available.
This can be useful, for example, if it is possible that the data from two consecutive
responses may be identical.
NOTE: In the specific case of the gateway’s default configuration, the “Trigger byte”
element for responses to the “Transactions 1” and “Transactions 2” personalized
commands of the “TeSys U n°1” node is set to “Enabled”. Hence, the management of
responses to read and write commands for parameters is event driven.
The “Trigger byte address” elements of the “Response” elements for these two commands
are configured at addresses 0x001E and 0x001F. These are the “parameter read/write
response counters”. Considered under DeviceNet and RSNetWorx, these two data are
configured the same way as the other inputs (see chapter 4.2.6 Configuring Inputs from the
Gateway) and both correspond to the I:1.16 input.
The DeviceNet master PLC will be able to detect the receipt of a response from a Modbus
slave by comparing the previous value and the current value of the associated counter
(address 0x001E or 0x001F). If there is a unitary incrementation of this counter, the PLC
may, for example, read all of the data from the response (addresses 0x0013 to 0x0017 or
addresses 0x0018 to 0x001D) and allow the transmission of a new query for reading or
writing the value of a parameter (using a “Trigger byte” for the queries). In contrast to other
“Query” counters, the value stored at the “Response” Trigger byte Address is a true
modulo 256 counter, i.e. zero must be managed (… 254, 255, 0, 1, 2 …).
In this example using the ATS48, we do not want the response to be event driven. So we will be retaining the
default configuration.