Fire Detection Product Catalogue
Z132A Sounder Base
The Z132A Sounder Base provides mounting
facilities and an inbuilt audible alarm for the 130
Series detectors. The sounder actuates whenever its
associated detector enters an alarm state, providing
a 90dB signal at a distance of 3 metres. To ensure
that the sounder operation does not interfere with
normal detector operation, the Z132A requires
a separate 24Vdc supply that is electrically and
physically separated from the detector supply. For
supervision of the 24V line, an ADM131 Monitor
Module and 24V relay may be used. For activation of
a group of sounders from any one group of detectors,
an ADC130 Control Module and 24V relay is used.
Specifications
Sounder Supply Voltage 17 to 32Vdc
Sounder On Current
15mA
Sounder Off Current
1mA
Loop Current (quiescent) 0μA
Loop Current (alarm)
700μA
Quiescent Current (max.) 250μA
Sounder Output
90dBA at 3m
Relative Humidity
10% to 95% (n/cond)
Ambient Temperature
-5°C to +45°C
Weight
187g
CSIRO ActivFire Listed with 130 series detectors
FPANZ Listed
VF/413
Z132A
Part Number
130 Series Detector Bases
Specifications
Sounder Supply Voltage 17 to 32Vdc
Relative Humidity
10% to 95% (n/cond)
Ambient Temperature
-5°C to +45°C
Weight
187g
CSIRO ActivFire Listed with 130 series detectors
FPANZ Listed with 130 series detectors
Part Numbers
The SMB600 Mounting Base consists of the
following parts:
1x Plastic surface mount base
2x #6 x 1” sheet metal screws
2x #8-32 x 1/2” screws
2x Plastic anchors
Z131A
Analogue Detector Base
The Z131A Detector Base should be mounted on a
flat surface with suitable fasteners.
SMB600
Series 130 Mounting Base
The D51Z131 Duct Sampling Unit consists of
a D51B duct housing fitted with a Z131 base in
readiness for fitting an analogue addressable P131
photoelectric smoke detector. The DSU is designed
to sample air in air conditioning ducts and pass
the air through the smoke detector. The D51B is
fixed on the outside of the duct to be sampled,
allowing easy access for detector servicing and
replacement of the dust filter. To cater for most
duct sizes, a sampling tube extension is available in
3 metre lengths. The Tyco E500 Mk2 Series Remote
Indicators can be used for remote indication of an
alarm.
Specifications
Duct Pressure*
-1.15 to +3.0 kPa
Sampling Tube Length
160mm minimum
Max. Duct Width
1.8m
Remote Indicator
E500 Mk2 Series
Not CSIRO ActivFire Listed
Part Numbers
D51Z131
Z131 Base fitted
D51L
Baffle box of 10
D51F
Filter box of 10
D51T3
3m Sampling Tube
D51K100
Sampling Tube End Cap
(packet of 10)
D51Z131 Duct Sampling Unit
*AS 1603.13-1998 test
www.simplexfire.com.au