Download Fire Detection - Australia
Transcript
Fire Detection Product Catalogue Z132A Sounder Base The Z132A Sounder Base provides mounting facilities and an inbuilt audible alarm for the 130 Series detectors. The sounder actuates whenever its associated detector enters an alarm state, providing a 90dB signal at a distance of 3 metres. To ensure that the sounder operation does not interfere with normal detector operation, the Z132A requires a separate 24Vdc supply that is electrically and physically separated from the detector supply. For supervision of the 24V line, an ADM131 Monitor Module and 24V relay may be used. For activation of a group of sounders from any one group of detectors, an ADC130 Control Module and 24V relay is used. Specifications Sounder Supply Voltage 17 to 32Vdc Sounder On Current 15mA Sounder Off Current 1mA Loop Current (quiescent) 0μA Loop Current (alarm) 700μA Quiescent Current (max.) 250μA Sounder Output 90dBA at 3m Relative Humidity 10% to 95% (n/cond) Ambient Temperature -5°C to +45°C Weight 187g CSIRO ActivFire Listed with 130 series detectors FPANZ Listed VF/413 Z132A Part Number 130 Series Detector Bases Specifications Sounder Supply Voltage 17 to 32Vdc Relative Humidity 10% to 95% (n/cond) Ambient Temperature -5°C to +45°C Weight 187g CSIRO ActivFire Listed with 130 series detectors FPANZ Listed with 130 series detectors Part Numbers The SMB600 Mounting Base consists of the following parts: 1x Plastic surface mount base 2x #6 x 1” sheet metal screws 2x #8-32 x 1/2” screws 2x Plastic anchors Z131A Analogue Detector Base The Z131A Detector Base should be mounted on a flat surface with suitable fasteners. SMB600 Series 130 Mounting Base The D51Z131 Duct Sampling Unit consists of a D51B duct housing fitted with a Z131 base in readiness for fitting an analogue addressable P131 photoelectric smoke detector. The DSU is designed to sample air in air conditioning ducts and pass the air through the smoke detector. The D51B is fixed on the outside of the duct to be sampled, allowing easy access for detector servicing and replacement of the dust filter. To cater for most duct sizes, a sampling tube extension is available in 3 metre lengths. The Tyco E500 Mk2 Series Remote Indicators can be used for remote indication of an alarm. Specifications Duct Pressure* -1.15 to +3.0 kPa Sampling Tube Length 160mm minimum Max. Duct Width 1.8m Remote Indicator E500 Mk2 Series Not CSIRO ActivFire Listed Part Numbers D51Z131 Z131 Base fitted D51L Baffle box of 10 D51F Filter box of 10 D51T3 3m Sampling Tube D51K100 Sampling Tube End Cap (packet of 10) D51Z131 Duct Sampling Unit *AS 1603.13-1998 test www.simplexfire.com.au Page 19