Download HVX9000 AF Drives
Transcript
HVX9000 Drive User Manual November 2003 Table B-12: Parameter Group G1.12: Preset Speeds Code Parameter Range Step Default ID # Description Page P1.12.1 #1 Preset Speed 0.0 – 100.0 0.1% 10.0 1600 Defines #1 preset speed as a percentage of Max Frequency. 8-57 P1.12.2 #2 Preset Speed 0.0 – 100.0 0.1% 20.0 1601 Defines #2 preset speed as a percentage of Max Frequency. 8-57 P1.12.3 #3 Preset Speed 0.0 – 100.0 0.1% 30.0 1602 Defines #3 preset speed as a percentage of Max Frequency. 8-57 P1.12.4 #4 Preset Speed 0.0 – 100.0 0.1% 40.0 1603 Defines #4 preset speed as a percentage of Max Frequency. 8-57 P1.12.5 #5 Preset Speed 0.0 – 100.0 0.1% 50.0 1604 Defines #5 preset speed as a percentage of Max Frequency. 8-57 P1.12.6 #6 Preset Speed 0.0 – 100.0 0.1% 75.0 1605 Defines #6 preset speed as a percentage of Max Frequency. 8-57 P1.12.7 #7 Preset Speed 0.0 – 100.0 0.1% 100.0 1606 Defines #7 preset speed as a percentage of Max Frequency. 8-57 ID # Description Page Table B-13: Parameter Group G1.13: Communication Bus Code Parameter Range Step Default P1.13.1 FBDataOut1Sel 0 – 10000 1 1590 852 (Motor speed – %) Motor Speed (Percent) 8-58 P1.13.2 FBDataOut2Sel 0 – 10000 1 1 (Output frequency – Hz) Output Frequency (Hz) 8-58 P1.13.3 FBDataOut3Sel 0 – 10000 1 25 854 (Frequency reference – Hz) Frequency Reference (Hz) 8-58 P1.13.4 FBDataOut4Sel 0 – 10000 1 2 (Motor speed – rpm) 855 Motor Speed (rpm) 8-58 P1.13.5 FBDataOut5Sel 0 – 10000 1 1780 (Motor current) 856 Motor Current 8-58 P1.13.6 FBDataOut6Sel 0 – 10000 1 5 (Motor power) 857 Motor Power 8-58 P1.13.7 FBDataOut7Sel 0 – 10000 1 1701 1701 (Motor run time – minutes) Motor Run Time (Minutes) 8-58 P1.13.8 FBDataOut8Sel 0 – 10000 1 1666 (Energy meter – kW) Energy Meter (Kilowatts) 8-58 TD04008003E 853 1666 For more information visit: www.eatonelectrical.com B-13