Feeder Protection and Control Unit (PAC-P100) User’s Manual
/ SETTING / PROTECT. / SGR
This menu is used to set values for the sensitive ground protection element. It is used to
enable/disable functioning and event recording for SGR, to set pickup start voltage/current
values and operation delay time, and to select an internal input element and block this protection
function. If “Function” item is set to disabled, SGR protection element is not used and events
are not recorded. But, only “Event” item can be disabled to prevent event recording for SGR,
while SGR protection element is still being used. Pickup values range from 5 to 50 V with 1 V
value step for voltage and from 0.9 to 9.8 mA with 0.1 mA value step for current. Operation
time delay moves from 1.0 to 10.0 sec with 0.1 sec value step. “Block” set to ‘COLD LD OP’ of
<Table 4.3.2 EasyLogicTM Operand>, for example, when SGR protection element is to be
inhibited if cold load pickup protection is operated. This protection element is used for the
ground protection of non-grounded network.
S GR
⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯
1 . F u n c t i o n
:
E n a b l e d
2 . V o l t .
P i c k u p :
5 0
[ V ]
3 . C u r r .
P i c k u p :
9 . 8
[ mA ]
4 . O P
T i m e
:
3 0 . 0 0
[ s e c ]
5 . MT A
:
+ 4 5
[ ° ]
6 . B l o c k
:
L _ O F F
7 . E v e n t s
:
D i s a b l e d
⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ ⎯
← : E s c a p e , ↑ ↓ : M o v e , → : S e l e c t
[SGR setting items]
1)
2)
3)
4)
5)
Function
Volt. Pickup
Curr. Pickup
OP Time
Block
6) Events
56/94
use or non-use of SGR, Enabled / Disabled
pickup start voltage, 5 ~ 50 V step: 1 V
pickup start current, 0.9 ~ 9.8 mA step: 0.1 mA
operation time delay, 0.05~30.00 sec step: 0.01 sec
internal input element for blocking SGR
Refer to <Table 4.3.2 EasyLogicTM Operand>
event recorded or not for SGR, Enabled / Disabled