Serial Communications \Remote Analog Output Calibration Procedure (cont.)
Exit Jog Mode
1) Open the MS332 Run Switch
2) Un-assign the Jog Switch-Input function from the Switch-Input by writing 0 to the corresponding Switch-Input
function assignment variable.
Example: If you previously wrote 1 (Jog) to Var07.03 (address 47030) assigning Jog to Switch-Input 4,
write 0 to it now to un-assign Jog from it.
Ref. Sect. page - 57