RTXMIT: Full duplex Transfer (Compact, Momentum, Quantum)
Runtime Errors
Error code (at
StatusTx and
StatusRx
Error code (at StatusTx and StatusRx
Error Code Description
0
No error, either EFB is turned off completely (TxStart and RxStart are FALSE)
or the ongoing process works properly.
8003 (hex)
The assigned Modbus port does not exist (>1 on Quantum and Compact, >2
on Momentum).
or
Another EFB is using the assigned Modbus port already.
132
8304 (hex)
The assigned Modbus port is used by a 984-Loadable (like XMIT).
8305 (hex)
Illegal baudrate being assigned.
8307 (hex)
Illegal number of data bits being assigned.
8308 (hex)
Illegal number of stop bits being assigned.