Download SIEMENS
Transcript
SIEMENS 11.2.2 Relay Module (LZY40) The Relay Module is the plant actuator. When one assigned sensor detects gas presence, the LZY40 activates the corresponding internal relay, provided with a voltage free changeover contact 250VAC, 5A: 1. K2: Pa (pre-alarm) 2. K3: 1T (first alarm threshold) 3. K4: 2T (second alarm threshold) 4. K1: fault (FA) The relay operation logic can be selected from the Central Unit (positive or negative) There are 5 front panel LEDs for relay and operating status monitoring: - Red LED (high) - Yellow LED - Red LED (3) Power supply Power consumption Protection degree Allowable room temperature Allowable room humidity User Manual - LYC40 Rev.06 September 2001 Operating status: fast blinking = LZY40 not configured slow blinking = LZY40 configured steady on = alarm or fault Module fault relay status (FA) Pre-alarm relay status (Pa) First alarm threshold relay status (1T) Second alarm threshold relay status (2T) 12VDC 2.5VA max IP42 (vertical mounting) 0…50°C 20…90% RH non condensing 85 Siemens Building Technologies HVAC Products