Download User`s Manual for Installation and Configuration
Transcript
Chapter 4. FUNCTIONS NECESSARY FOR CONTROL ● PV bank (high and low limits of linear range) The high and low limits of the linear range need to be set when the DC voltage or DC current is selected for the input type. Input high and low limit values corresponding to the output range (engineering range) of the connected unit. Example: Setting when the pressure transmitter is connected (Pv-0 1 41: 4 to 20 mA is selected) Specifications of transmitter Output signal Output range Setting of this unit Item display Item name Settings 4 mA DC 0.0 kPa Pv-09 Linear scaling low limit 0.0 20 mA DC 10.0 kPa Pv- 10 Linear scaling high limit 10.0 (1) Keep the [para] key pressed for 2 s in the operation display status. >> MOde is flashing on the upper display. MODE (2) Press the [ ] key or [para] key several times until Pv is shown on the upper display. >> Pv is flashing on the upper display. PV (3) Press the [enter] key. >> Pv-0 1 is shown on the upper display. At this time, check that 1. is shown on the auxiliary display. (To set input 2, change the value with the [>] key or [<] key.) PV-0 1 1. 51 (4) Press the [ ] key several times until Pv-09 is shown on the upper display. >> Pv-09 is shown on the upper display. PV-09 1. 0.0 (5) Press the [enter] key. >> The value on the lower display starts flashing. PV-09 1. 0.0 (6) Set at 0.0 with the [ ] key or [ ] key. (7) Press the [enter] key to set the value. 4-6