Download "user manual"
Transcript
7.1.4 Test Mode The test mode enables you to select which measuring value (active, reactive, I2, U2) is output to the optical test output. In the display, values for active, reactive and apparent energy are available. Depending on parameter setting, the resolution of the display register can be increased for faster testing. In the test mode, the resolution is increased by one decimal point compared with the normal mode. A maximum of 5 decimal points are possible. 1. 2. 3. 4. Select test mode Test mode Enter test mode First value Select required value Value x Repeat step 3 for all values to be tested Operating display Exit test mode 5. Examples Note First value and value x are examples. The real values are defined in the parameter settings and are the same as the operating display. The measured values are displayed at the optical test outputs as shown in the following table: Mode Register on Display Test output reactive Test output active Normal mode Some sort of register |R| |A| Test mode NLA register I2 with RCU=1Ω U2 with RFE=1MΩ U2 with RFE=1MΩ I2 with RCU=1Ω Reactive energy register |A| |R| Active energy register or one of not mentioned registers in this table. |R| |A| (Transformer losses per phase NLA1,NLA2,NLA3; Total Transformer Losses NLA) OLA register (Line losses per phase OLA1, OLA2, OLA3; Total line losses OLA) © Landis+Gyr AG 88/108 H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual Maintenance