200 V Class Inverters of 22 kW, 45 kW, 55 kW and 400 V Class Inverters of 18.5 kW to 75 kW Removing the Cooling Fan 1. Remove the terminal cover, Inverter cover, Digital Operator, and front cover from the front of the Inverter. 2. Pull the cooling fan power cable connector that extends from the fan cover cable hole out of the cooling fan power relay board. 3. Remove the fan cover screws and pull out the fan cover from the Inverter. 4. Remove the cooling fan from the fan cover and replace it with a new one. Mounting the Cooling Fan After attaching a new cooling fan, reverse the above procedure to attach all of the components. Refer to the next page for attaching the fan cover. When attaching the cooling fan to the mounting bracket, be sure that the airflow faces the top of the Inverter. Front cover mounting screws Front cover Terminal cover Terminal cover mounting screws Circulation fan mounting screws Fan cable pullout position Circulation fan Airflow direction Fan support mounting screws Fan support Fan support Airflow direction Cooling fans Fan power relay board Cooling fans Cooling fan mounting screws Cooling fan mounting screws Fan power cable pullout position Fig 8.3 Cooling Fan Replacement (200 V Class Inverters of 45 kW and 55 kW) 8-8