Download Manual
Transcript
3-3 OUPUT CONNECTIONS 1. Verify that power source to the unit is OFF, locked and tagged according to OSHA requirements. CAUTION Verify that the output voltage as stated on the UPS nameplate matches the actual output voltage of the unit. Ensure that the intended connected load does not exceed unit capacity. If the voltage does not match, or the intended applied load exceeds unit capacity, STOP installation of the UPS and contact Customer Service at DSPM. 2. Verify that Output cable(s) and conduit(s) are routed correctly and are in position to connect the unit. 3. Open front doors of UPS. 4. Select desired mounting location and connect the conduit. 5. Pass wires through the mounting hole. 6. Secure conduit fitting to the panel of unit. 7. Connect the output wires to the output phase, neutral and ground terminal blocks. Note: Ensure that the applied loads wired to the unit are evenly balanced. Loads to be evenly distributed to all output circuit breakers provided. Output Terminal Blocks (TB2), 3 Phase, Neutral, Ground (X1, X2, X3, XO, G) Note: If output Options where ordered with the unit they will be connected to the Main Output Terminals. Phone: (714) 970-2304 Fax: (714) 970-6171 Web Page: www.DSPManufacturing.com Email: [email protected] 21