71
BIS C-6021
Opening the processor / Interface information
To convert the processor for the power supply via the installation remote bus instead of supplying it via X1, the internal connections have to be changed.
Opening the
BIS C-6021
processor
Ensure that the device is turned off. Remove the 4 screws on the BIS C-6021 and lift off the
cover. Conversion see the following .
Head 2 Head 1
Connection for read/write head 2
Connection for read/write head 1
Be sure before
opening that the
unit is disconnected
from power.
Digital input,
X1
power supply for ST9
remote bus version
Connection locations
and names
INTERBUS output
X2
INTERBUS input
X3
deutsch
Connection diagram
for BIS C-6021
processor
Mounting of the cover
(4 screws),
max. permissible tightening
torque: 0.15 Nm
Service interface X4
Function ground FE
E
71
72
BIS C-6021
Interface Information / Wiring Diagrams
To make the connections for the InterBus, the supply voltage and the digital input, connect
the pre-assembled cable to the processor. For additional wiring information, see the
following .
Connect the read/write heads to the terminals for Head 1 and Head 2.
Connecting on the
remote bus or
installation remote
bus
The BIS C-6021...ST8 processor is intended for use on the installation remote bus, which
provides the supply voltage over the bus. The BIS C-6021...ST9 processor is intended for use
on the remote bus, whereby the supply voltage for the processor is brought in through X1.
Connect the incoming INTERBUS cable to the INTERBUS input X3. Connect the outgoing
INTERBUS cable to the INTERBUS output X2.
If this remote bus station is the last one on the bus, the INTERBUS output X2 must be closed
off with a threaded cap to maintain the enclosure rating.
☞
72
E
Please note the load capacity of the INTERBUS cable and verify during operation that the supply
voltage is maintained at the processor (see Technical Data for specifications).