Download Advantys STB - Maintenance
Transcript
Analog Input Modules absolute accuracy (RTD errors not included) 50 Ω US/JIS Pt100 four-wire two- or three-wire 20 Ω US/JIS Pt1000 four-wire 500 Ω two- or three-wire 200 Ω Ni100 four-wire 50 Ω two- or three-wire 20 Ω Ni1000 four-wire 500 Ω two- or three-wire 200 Ω Cu10 four-wire 50 Ω two- or three-wire 20 Ω Pt @ 25° C (77° F) +/- 0.5 degrees C Cu @ 25° C (77° F) +/- 2.0 degrees C +/- 0.9 degrees F +/- 3.6 degrees F Ni @ 25° C (77° F) +/- 0.5 degrees C +/- 9.0 degrees F Pt @ 60° C (140° F) +/- 2.0 degrees C Cu @ 60° C (140° F) +/- 4.0 degrees C +/- 3.6 degrees F +/- 6 degrees F Ni @ 60° C (140° F) +/- 1.6 degrees C +/- 1.6 degrees F * Requires the Advantys configuration software. TC Specifications temperature unit default degrees C user configurable* degrees C or degrees F data resolution increments of 0.1 degree (C or F) broken wire detection monitored independently on each channel TC sensor types type J user-configurable* -210 ... +1200 degrees C -346 ... +2192 degrees F type K -270 ... +1370 degrees C -454 ... +2498 degrees F type E -270 ... +1000 degrees C -454 ... +1832 degrees F 31007715 6/2008 171