Analog Output Modules fallback states (when predefined is the fallback mode) default 0 mA on both channels user-configurable integer values between 0 ... 32 000 on each channel, representing a state between 0 ... 20 mA settings1 addressing requirement two words for output data plus one for the power-down state configuration parameter actuator bus power for accessories 100 mA/channel @ 30 degrees C 50 mA/channel @ 60 degrees C over-current protection for accessory power yes field power requirements from a 24 VDC PDM power protection time-lag fuse on the PDM explosive & maritime environment applications ATEX and FM Class 1, Div. 2 certified, @ 0 to 60°C with an operating voltage of 19.2 to 30 VDC *ATEX applications prohibit hot swapping-refer to the Advantys STB System Planning and Installation Guide, 890 USE 171 **Basic NIMs do not allow you to hot swap I/O modules. 1 Requires the Advantys configuration software. Note: The field actuators or inputs driven by these nonisolated output channels must be independent (isolated). Cross-channel errors can be generated if nonisolated inputs or actuators are used. 31007715 6/2008 319