Analog Input Modules
absolute
accuracy
(RTD errors
not included)
50 Ω
US/JIS Pt100
four-wire
two- or three-wire
20 Ω
US/JIS Pt1000
four-wire
500 Ω
two- or three-wire
200 Ω
Ni100
four-wire
50 Ω
two- or three-wire
20 Ω
Ni1000
four-wire
500 Ω
two- or three-wire
200 Ω
Cu10
four-wire
50 Ω
two- or three-wire
20 Ω
Pt @ 25° C (77° F)
+/- 0.5 degrees C
Cu @ 25° C (77° F)
+/- 2.0 degrees C
+/- 0.9 degrees F
+/- 3.6 degrees F
Ni @ 25° C (77° F)
+/- 0.5 degrees C
+/- 9.0 degrees F
Pt @ 60° C (140° F)
+/- 2.0 degrees C
Cu @ 60° C (140° F)
+/- 4.0 degrees C
+/- 3.6 degrees F
+/- 6 degrees F
Ni @ 60° C (140° F)
+/- 1.6 degrees C
+/- 1.6 degrees F
* Requires the Advantys configuration software.
TC
Specifications
temperature unit
default
degrees C
user configurable*
degrees C or degrees F
data resolution
increments of 0.1 degree (C or F)
broken wire detection
monitored independently on each channel
TC sensor types
type J
user-configurable*
-210 ... +1200 degrees C
-346 ... +2192 degrees F
type K
-270 ... +1370 degrees C
-454 ... +2498 degrees F
type E
-270 ... +1000 degrees C
-454 ... +1832 degrees F
31007715 6/2008
171