Download Product Guide Fire Detection Systems
Transcript
Chapter 4 Fire Detection Control Panels Series BC600 211241 45 Fire Detection Control Panel BC600-16L4S The modularly constructed Fire Detection Control Panel BC600-16L4S comprises a wall-mount cabinet with a display and operating field, a Power Supply NT604-1 with an output current of 4.2A, a Backplane BPL610-1 with a Central Processing Board ZTB600-1 and 8 free mounting positions as well as a Module Carrier BGT600-1. In addition, the unit offers the following specific features: If an optional Backplane BPL608-1 is installed, 8 additional mounting positions for function modules are available. As a result, the control panel housing can be equipped with a maximum of 16 function modules (e.g., Conventional Detector Interface GIF608-1, Loop Interface LIF601-1, Fire Brigade Interface FWI600-1). The integrated display and operating field consists of a 1/4 VGA graphics display, the LED displays as well as a membrane keypad. The door of the housing is provided with 4 mounting spaces for optional expansions such as a LED/button field, a front panel printer or a fire brigade control unit. At the bottom of the cabinet, there is space for stand-by batteries with 2 × 12V/max. 45Ah. Further features and functions are listed in the description of the Fire Detection Control Panel Series BC600. Specifications Mains voltage Output voltage Output current of power unit Output current of siren outputs Ambient temperature Dimensions W × H × D Colour of housing Weight without battery Approvals Cross-references Page 49 45 47 47 46 68 67 48 66 211112 230VAC +10/-20%, 47...63Hz typ. 27.6VDC max. 4.2A max. 1A per output -5°C to +50°C 480 × 660 × 190 (mm) grey white, RAL 9002 approx. 11.7kg VdS pending Art.No. Name Type 211151 211112 211113 211117 211110 222010 222004 211119 223026 Backplane BPL608-1 Conventional Detector Interface GIF608-1 Fire Brigade Interface FWI600-1 LED Display Field LAF648-1 Loop Interface LIF601-1 Relay Module 4-Fold/230VAC RL58-2 Relay Module 8-Fold/60VDC RL58-1 Serial Interface SIF601-1 Siren Connection Module SZ58-3 Conventional Detector Interface GIF608-1 The Conventional Detector Interface GIF608-1 supports 8 detector lines in addressable conventional technology in Fire Detection Control Panels Series BC600. The detector lines can be parameterised individually as: Detector lines for fire alarm for the connection of manual call points as well as automatic detectors with or without alarm verification Detector lines for technical messages for the connection of monitoring and condition detectors Detector lines for fault messages for the connection of fault detectors System inputs for special purposes (e.g., to accept control commands) Confirmation inputs for monitoring of acuations and transmitting devices Each detector line can be assigned either to a logic detector zone or to a zone element. In this way, it is also possible to unite several detector lines in one detector zone, hence allowing to operate them together. The end-of-line element - resistor or capacitor - can also be parameterised. If necessary, detector lines can also be configured as inputs without monitoring. In addition, the Conventional Detector Interface GIF608-1 is equipped with 8 freely parameterisable opencollector outputs for general control tasks. Features Independent microprocessor to ensure the alarming capability of every detector even at system failure of the control panel Individual detector identification for up to 64 addresses per detector line in conjunction with optional address modules Detector lines monitored for wire breakage, short circuit and earth fault All inputs and outputs accessible via pluggable screw terminals 01 / EX11399E.SAM /1039-01/0100