Download Product Guide Fire Detection Systems

Transcript
Chapter 4 Fire Detection Control Panels Series BC600
211241
45
Fire Detection Control Panel BC600-16L4S
The modularly constructed Fire Detection Control Panel BC600-16L4S comprises a wall-mount cabinet
with a display and operating field, a Power Supply NT604-1 with an output current of 4.2A, a Backplane
BPL610-1 with a Central Processing Board ZTB600-1 and 8 free mounting positions as well as a Module
Carrier BGT600-1. In addition, the unit offers the following specific features:
If an optional Backplane BPL608-1 is installed, 8 additional mounting positions for function modules
are available. As a result, the control panel housing can be equipped with a maximum of 16 function
modules (e.g., Conventional Detector Interface GIF608-1, Loop Interface LIF601-1, Fire Brigade Interface FWI600-1).
The integrated display and operating field consists of a 1/4 VGA graphics display, the LED displays as
well as a membrane keypad.
The door of the housing is provided with 4 mounting spaces for optional expansions such as a LED/button field, a front panel printer or a fire brigade control unit.
At the bottom of the cabinet, there is space for stand-by batteries with 2 × 12V/max. 45Ah.
Further features and functions are listed in the description of the Fire Detection Control Panel Series
BC600.
Specifications
Mains voltage
Output voltage
Output current of power unit
Output current of siren outputs
Ambient temperature
Dimensions W × H × D
Colour of housing
Weight without battery
Approvals
Cross-references
Page
49
45
47
47
46
68
67
48
66
211112
230VAC +10/-20%, 47...63Hz
typ. 27.6VDC
max. 4.2A
max. 1A per output
-5°C to +50°C
480 × 660 × 190 (mm)
grey white, RAL 9002
approx. 11.7kg
VdS pending
Art.No.
Name Type
211151
211112
211113
211117
211110
222010
222004
211119
223026
Backplane BPL608-1
Conventional Detector Interface GIF608-1
Fire Brigade Interface FWI600-1
LED Display Field LAF648-1
Loop Interface LIF601-1
Relay Module 4-Fold/230VAC RL58-2
Relay Module 8-Fold/60VDC RL58-1
Serial Interface SIF601-1
Siren Connection Module SZ58-3
Conventional Detector Interface GIF608-1
The Conventional Detector Interface GIF608-1 supports 8 detector lines in addressable conventional technology in Fire Detection Control Panels Series BC600. The detector lines can be parameterised individually as:
Detector lines for fire alarm for the connection of manual call points as well as automatic detectors
with or without alarm verification
Detector lines for technical messages for the connection of monitoring and condition detectors
Detector lines for fault messages for the connection of fault detectors
System inputs for special purposes (e.g., to accept control commands)
Confirmation inputs for monitoring of acuations and transmitting devices
Each detector line can be assigned either to a logic detector zone or to a zone element. In this way, it is also possible to unite several detector lines in one detector zone, hence allowing to operate them together.
The end-of-line element - resistor or capacitor - can also be parameterised. If necessary, detector lines can
also be configured as inputs without monitoring.
In addition, the Conventional Detector Interface GIF608-1 is equipped with 8 freely parameterisable opencollector outputs for general control tasks.
Features
Independent microprocessor to ensure the alarming capability of every detector even at system failure
of the control panel
Individual detector identification for up to 64 addresses per detector line in conjunction with optional
address modules
Detector lines monitored for wire breakage, short circuit and earth fault
All inputs and outputs accessible via pluggable screw terminals
01 / EX11399E.SAM
/1039-01/0100