LIMITS SETUP
! IMPORTANT:
1.
Before the initial limits setup, a Positive Stop MUST be installed at the close position.
This will be used as a reference to relearn the limit positions if the gate has been
operated manually while released or if the EPS2 Cable has been disconnected.
2. In the event of a complete power failure, including battery backup, the
limit positions may have may been cleared and will need to be reset as described.
STEP 1
Connect the “Motor Harness” to the
Control Board.
1a
1b
a. “OPEN LEFT” Connector if the gate
opens to the Left, when viewed from
inside.
b. “OPEN RIGHT” Connector if the gate
opens to the Right, when viewed from
inside.
STEP 2
STEP 3
Move the gate to the desired close
position then press and hold the “Close
Limit” button until the LED is solid.
Move the gate to the desired open
position then press and hold the “Open
Limit” button until the LED is solid.
“Close Limit” LED
flashes if the close
limit is not set.
STEP 4
Run the gate in the close direction to
search for the installed Positive Stop.
This will be used as a reference.
20
“Open Limit” LED
flashes if the open
limit is not set.
! NOTE: For this 1st cycle, the gate will
run slowly past the set close limit,
contact the Positive Stop and reverse
back.