Download SMA SB2000-2500-3000HF
Transcript
SMA Solar Technology AG Event no. Display message and cause 2 < Grid fault > The line voltage has fallen below the permissible range. This error can have the following causes: 3 Messages Corrective measures • Check for tripping of the miniature circuit‑breaker. • Check the grid voltage and connection on the inverter. • Power distribution grid disconnected If the line voltage lies outside the permissible range due to local grid • AC cable damaged conditions, ask your grid operator if the • The grid voltage at the termination voltage can be adjusted at the feeding point of the inverter is too low. point or if it would be acceptable to The inverter disconnects itself from the change the monitored operational limits. power distribution grid for safety reasons. If the grid voltage lies within the tolerance range, yet this error is still being displayed, contact the SMA Service Line. • Check the grid voltage at the < Grid fault > termination point of the inverter: The 10‑minute average line voltage is no longer within the permissible range. This can have the following causes: • The grid voltage at the termination point of the inverter is too high. • Grid impedance at the termination point of the inverter is too high. The inverter disconnects to assure compliance with the power quality of the power distribution grid. 4 < Grid fault > 5 The inverter is no longer in grid parallel operation and has stopped feed‑in operation for safety reasons. < Grid fault > If, due to local grid conditions, the grid voltage exceeds the configured limiting value, ask the grid operator whether the voltage can be adjusted at the feeding point, or whether it would be acceptable to modify the limiting value for power quality monitoring. If the grid voltage is continuously within the tolerance range, and this error is still displayed, contact the SMA Service Line. • Check the grid connection for strong, short‑term frequency variations. • If possible, check the power frequency and observe how often The power frequency is not within the major deviations occur. permissible range. The inverter disconnects itself from the power distribution grid for If there are frequent fluctuations and this safety reasons. error occurs as a result, ask your grid operator if it would be acceptable to change the operating parameters. Discuss the proposed parameters with the SMA Service Line. Installation Manual SB20HF-30HF-IA-IEN120431 67