Download warning - LUCKINSlive
Transcript
Checks Reference in this Manual Done Remarks On IO Scanning configuration of the sender Configuration of the IO Scanning Service PLC, check that: (see page 120) z The data are sent in 1 block with a write request to the receiver PLC. z The Health Timeout (ms) parameter value is equal to 300 ms or to the minimum value allowed by the conditions of the communication. z The WR length parameter is set to 100. z The value in WR Master Object parameter fits to the source address of DATA_SAFE output parameter (S_WR_ETH DFB) on sender PLC program. z The value in WR Ref Slave parameter fits to the address of INPUT_DATA input parameter (S_RD_ETH DFB) on receiver PLC program. z In the receiver PLC, the memory area where the data will be written is located in the unrestricted memory area. z The Repetitive rate (ms) value is equal to the receiver PLC cycle time. 136 If safe peer-to-peer communication is used, monitor the status of the NTP synchronization (%SW39 or SYNCHRO_NTP output parameter of the S_RD_ETH and S_WR_ETH function blocks) and signal a detected fault to the maintenance personnel. NTP Server Time Consistency and System Bits (see page 114) If safe peer-to-peer communication is used, monitor the status of the HEALTH output parameter of the S_RD_ETH function block. Configuration of S_RD_ETH DFB in the User Program of the Receiver PLC (see page 117) 33003879 04/2013