Download Nuaire`s Residential Heat Recovery Catalogue.
Transcript
Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 23 MECHANICAL VENTILATION & HEAT RECOVERY 23 FAN TYPE FAN LOCATION MAX PERFORMANCE MRXBOX95-WALL WALL/CUPBOARD 52l/s 24 MRXBOX95-WH1 WALL/CUPBOARD 110l/s 30 MRXBOX95-LOFT LOFT 64l/s 36 MRXBOX95-LH1 LOFT 113l/s 44 MRXBOX95-LH2 LOFT 132l/s 52 MRXBOX90-L WALL/LOFT 125l/s 60 LPXBOXDC-2 CEILING VOID 75l/s 64 COOKERXBOX KITCHEN 54l/s 68 nuaire.co.uk PAGE 23 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 24 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N MRXBOX95-WALL MECHANICAL SUPPLY & EXTRACT WITH HEAT RECOVERY UP TO 95% EFFICIENT, SAP APPENDIX Q RECOGNISED. WALL/CUPBOAD MOUNTING DESIGN FOR SMALL TO MEDIUM HOUSES & APARTMENTS. 24 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 25 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N B E NE F I T S MRXBOX95-WALL is designed to provide optimised balanced (supply and extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas, creating comfortable well ventilated homes. MRXBOX95-WALL uses the latest generation of low voltage DC fans and motors, counter flow heat exchanger and easy accessible controls. The heat exchanger block can recover up to 95% of the normally wasted heat The two independent fans has full speed control for background and boost ventilation rates as well as a run-on timer facility. MEETS BUILDING REGULATIONS FLEXIBLE SOLUTION OPTIONAL SENSORS AND DETECTORS SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. MRXBOX95-WALL ensures a flexible solution with multi 125mm dia. spigots. Customise MRXBOX95-WALL for enhanced performance. All supplied with pre-plugged 10m data cable and incorporates status LED. EXTREMELY LOW NOISE LEVELS HIGH EFFICIENCY Quiet running unit ensuring occupant acceptability. Heat exchanger is up to 95% efficient. EASY INSTALLATION Compact, lightweight and simple to install. Full installation service available. FREE OF CHARGE CODE ADVISORY SERVICE Takes the stress out of specifying. WIDE CHOICE LOW MAINTENANCE REQUIREMENT Filter replacement typically every 12 - 18 months. Range of ducting and grilles available, please contact Nuaire. NO NEED FOR TRICKLE VENTS OPTIONAL SUMMER BYPASS AVAILABLE A cost saving and tenant acceptability. Provides cooling during warmer months. MRXBOX95B-WALL. IMPROVES INDOOR AIR QUALITY Prevents condensation by keeping moisture levels low - creating a healthier environment. 5 YEAR WARRANTY 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. INSTALLATION A 2 piece metal bracket is provided with the unit for wall mounting. One part of the bracket is mounted on the wall and the second part of the bracket is attached to the back of the unit. MRXBOX95-PIR (passive infra red) A low voltage sensor, detects movement and activates system. Incorporates overrun timer and timer adjustments. MRXBOX95-HUM A low voltage sensor, activates the system when the RH level is above set point. Incorporates overrun timer and RH setpoint level adjustment. MRXBOX95-RFI If fan failure occurs the audio visual indicator will flash a warning. REMOVABLE G2 FILTERS The unit and bracket are then installed onto the bracket on the wall. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 25 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 26 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N PERFORMANCE MRXBOX95-WALL Casing MRXBOX95 300 ISO 5801 2007 AMCA 300 V Fan Static Pressure (Pa) 250 Type D Air Density 1.2 kg/m3 200 150 Code descriptions 1 100 MR-XBOX-95-WALL | | | | 2 1 3 50 4 5 0 0 10.0 20.0 30.0 40.0 50.0 60.0 1. 2. 3. 4. 2 3 4 Multi-room supply and extract heat recovery Product range Efficiency Wall/cupboard application Air volume flow rate (l/s) SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange effIciency % Energy Saving Trust Best Practice Performance Compliant Kitchen Plus 1 wet room 0.59 92 Yes Kitchen Plus 2 wet rooms 0.68 91 Yes Kitchen Plus 3 wet rooms 0.83 90 Yes MRXBOX95-WALL E L E C T R I C A L & S OU N D Curve Maximum power consumption (Watts) 1 71 2 39 3 21 4 10 5 5 Open inlet Open outlet Breakout Open Inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Sound Power Levels dB re 1pW 63 125 250 500 1K 2K 4K 8K dBA @3m 45 48 51 44 44 50 42 42 48 40 40 46 35 36 42 47 59 51 44 53 48 37 49 44 32 43 38 20 33 28 41 54 43 36 48 38 31 42 32 23 33 23 5 18 8 39 47 38 34 41 33 26 35 27 18 20 18 11 3 24 39 30 20 29 25 20 23 19 12 14 10 - 24 33 26 19 25 21 17 19 15 9 13 6 - 30 41 33 26 36 30 21 31 26 16 24 21 <10 15 13 41 51 50 39 48 48 38 46 46 35 43 43 29 38 38 48 57 53 46 52 51 43 49 47 39 44 43 30 37 36 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving and based on SAP Appendix Q testing. 26 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 27 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N UNIT COMPONENTS Mounting bracket on wall and rear of unit. 4 3 1 2 Unit heat exchanger pod. Spigot Location & Ducting references Spigot 1. Spigot 2. Spigot 3. Spigot 4. Two Removable G2 filters. Removable access cover. Condensate tray. 125mm dia. = extract air from dwelling. 125mm dia. = exhaust air to outside. 125mm dia. = intake air from outside. 125mm dia. = supply air to house. DIMENSIONS (MM) Weight 13 Kg VIEW FROM FRONT WITH COVER REMOVED SIDE VIEW 435 Mounting bracket 21.5mm dia. condensate drain 598 VIEW FROM TOP 285 Mounting bracket Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 27 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 28 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Electrical details:Voltage: 240V 1ph 50Hz Consumption: 75W (max) 0.6 Amp Fuse rating: 3 Amp NOTE: This unit must be earthed. Detail of unit control on front panel. Power supply PCB. 230V in, 24V dc out. SL N L UNIT SERVING KITCHEN AND BATHROOM 230V IN 50Hz Mains Fan Unit MAINS 230V 50Hz N N L L Room light Fuse 2A SL 3 Pole isolator Light switch (Double Pole) Kitchen switch Earth point UNIT SERVING KITCHEN AND TWO BATHROOMS Fan Unit Internal wiring MAINS 230V 50Hz N N L L Room lights Fuse 2A Kitchen switch Connections for optional controls Volt free relay contacts Fault Run Switch to deactivate continuous trickle Fan connections 28 3 Pole isolator Light switches (Double Pole) Control PCB. 24V 029 2085 8200 SL Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:45 Page 29 MV H R MR XB OX95- WA L L TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI FIC ATION OPERATION OPTIONAL SUMMER BYPASS - MRXBOX95B-WALL The supply and extract system shall be wall/cupboard mounted in accordance with the specification. The bypass damper opens when a 230V signal is applied to the unit (via a manual switch, supplied). This opens the damper via an actuator. When the switch signal is de-activated the unit returns to its original state (air through the heat exchanger). Outside air supplied through the bypass is still filtered, so the air quality is optimal, irrespective of the bypass setting (Open or closed). The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from all wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches • Optional externally interconnected sensors When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. MRXBOX95-WALL - CONTROL OPTIONS All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Integral speed control on supply and extract. • Integral background ventilation control/set point. • Integral boost ventilation control/set point. • Integral run on timer. • Fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. An adjustable run-on facility is integrated into the unit which allows the fans to run-on for between 1 and 60 minutes after the signals have been switched off. OPTIONAL CONTROLS The unit shall have the facility to commission the supply and extract fans via inbuilt minimum and maximum speed adjustment; the fans shall have infinitely variable speed control. MRXBOX95-PIR Passive infra-red detector MRXBOX95-HUM Humidistat MRXBOX95-RFI Remote fail indictor Units shall be the MRXBOX95-WALL as manufactured by Nuaire. MRXBOX95-WALL - UNIT SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G2 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the front access panel, enabling quick and easy maintenance. The unit shall have low energy, high efficiency d.c. fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40ºC. The unit shall be supplied complete with an insulated condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 125mm circular ducting. D204 x 60mm. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 29 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 30 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N M RX B OX 9 5 - WH1 M E CHA NIC AL VENTILATION WITH HEAT RECOVERY UP TO 95% EFFICIENT, SAP APPENDIX Q RECOGNISED. WALL/CUPBOAD MOUNTING DESIGN FOR MEDIUM TO LARGE HOUSES & APARTMENTS. 30 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 31 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N B E NE F I T S MRXBOX95-WH1 is designed to provide optimised balanced (supply & extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas creating comfortable well ventilated homes. The unit has the facility to commission the supply & extract fans independently on both minimum and maximum speeds. The heat exchanger block can recover up to 95% of normally wasted heat. MEETS BUILDING REGULATIONS ADDED SECURITY SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. Windows may be kept closed. PRE-COMMISSIONING FILTER PROTECTION IMPROVES INDOOR AIR QUALITY OPTIMUM PERFORMANCE High efficiency filters helps to create a healthy living environment. Low Specific Fan power and high efficiency results in SAP Q. LOW & EASY MAINTENANCE SUITABLE FOR LARGER APPLICATIONS Designed to meet the duty for medium to large properties including 3 storey. Filters are covered in a removable protective film to prevent clogged up filters prior to occupant handover. SIMPLE FAN CONTROLS Easy accessible filters from front cover – no tools required. Filter replacement typically every 12 - 18 months. Independent controls for supply & extract for quick and easy commissioning. NO REQUIREMENT FOR TRICKLEVENTS Reduces noise from outside - overcome draught issues. DESCREET RUN MONITOR COMPACT Records units operational time. The unit fits easily into cupboards not taking up valuable storage space. INTEGRAL FROST PROTECTION 5 YEAR WARRANTY Protects the unit during extreme cold spells. 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. EXTREMELY LOW NOISE LEVELS Quiet running unit ensuring occupant acceptability. OPTIONAL SUMMER BYPASS AVAILABLE Provides cooling during warmer months. MRXBOX95B-WH1. INSTALLATION FEATURES Filter being removed Filter cover Typical cupboard installation of MRXBOX95-WH1. Download specification from www.nuaire.co.uk/specifications Removeable filters without removing front cover. nuaire.co.uk 31 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 32 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N PERFORMANCE Casing MRXBOX95-WH1 500 ISO 5801 2007 AMCA 300 V Type D Air Density 1.2 kg/m3 400 Fan Static Pressure (Pa) 1 300 Code description 2 MR-XBOX-95-WH1 | | | | 3 200 1 2 3 4 4 100 5 6 0 0 25 50 75 100 125 1. Multi-room supply and extract heat recovery 2. Product range 3. Efficiency 4. Wall/cupboard application 5. H1 = High 1 Model Air volume flow rate (l/s) MRXBOX95-WH1 E L E C T R I C A L & S OU N D Curve 1 Maximum power consumption (Watts) 150 2 114 3 75 4 36 5 14 6 8 Sound Power Levels dB re 1pW 63 125 250 48 51 58 56 63 67 56 61 59 48 50 57 56 62 66 56 60 58 47 50 56 55 62 65 55 60 57 46 48 53 54 60 62 54 58 54 44 45 50 52 57 59 52 55 51 41 42 44 49 54 53 49 52 45 Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open Inlet Open outlet Breakout Open inlet Open outlet Breakout 500 49 67 53 48 66 52 46 64 50 43 61 47 38 56 42 30 48 34 1K 47 62 43 45 60 41 43 58 39 37 52 33 30 45 26 19 34 <16 2K 39 60 40 37 58 38 35 56 36 29 50 30 22 43 23 <16 32 <16 4K 25 50 25 23 48 23 21 46 21 <16 40 <16 <16 33 <16 <16 22 <16 8K <16 41 <16 <16 39 <16 <16 37 <16 31 <16 <16 24 <16 <16 <16 <16 dBA @3m 31 47 33 30 45 32 29 44 31 25 40 28 22 35 24 <16 27 19 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving based on SAP Appendix Q testing. SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange efficiency % Energy Saving Trust Best Practice Compliant Application Specific fan power (W/l/s) Heat exchange efficiency % Energy Saving Trust Best Practice Compliant Kitchen Plus 1 wet room 0.41 91 Yes Kitchen + 5 wet rooms 0.62 89 Yes Kitchen Plus 2 wet rooms 0.40 91 Yes Kitchen + 6 wet rooms 0.72 88 Yes Kitchen Plus 3 wet rooms 0.46 90 Yes Kitchen + 7 wet rooms 0.83 87 Yes 0.53 90 Yes Kitchen + 4 wet rooms 32 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 33 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N GENERAL ARRANGEMENT MRXBOX95-WH1 Mounting bracket on wall and rear of unit. 4 1 3 2 Two removable G3 filters. Condensate tray. Spigot Location and Ducting references Spigot 1. 150mm dia. = extract air from dwelling. Spigot 2. 150mm dia. = exhaust air to outside. Spigot 3. 150mm dia. = intake air from outside. Spigot 4. 150mm dia. = supply air to house. MRXBOX95-WH1 - DIMENSIONS (mm) View from top Side view 16 458 Spigots 4 x 150mm dia. 619 226 120 Mounting bracket 226 View from front with cover removed 654 Download specification from www.nuaire.co.uk/specifications 431 nuaire.co.uk 33 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 34 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. The unit is supplied with a flexible cord for connection to the mains supply. Electrical details:Voltage: 240V 1ph 50Hz Consumption: WH1 - 1.3 Amp Fuse rating: 3 Amp NOTE: This unit must be earthed. Detail of unit control on front panel. Tamper proof label following commissioning. B L U The mains power supply cable should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. B R N B R N EXTRACT FAN RED YEL WHI BLU SUPPLY SWL RED YEL WHI BLU EXTRACT SUPPLY SUPPLY FAN B L U BYPASS FAIL Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is pre-wired with a 2 metre fly lead. UNIT SERVING KITCHEN AND BATHROOM Supply cord from unit MAINS 230V N 50Hz L Fuse 2A Light switch (Double Pole) Room light Blue Brown Black 3 Pole isolator Kitchen switch UNIT SERVING KITCHEN AND TWO BATHROOMS Green/yellow Blue Brown Black MAINS 230V N 50Hz L Fuse 2A Room lights Light switches (Double Pole) Kitchen switch 34 029 2085 8200 3 Pole isolator Supply cord from unit Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 35 MV H R MR XB OX95- W H 1 TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI FIC ATION OPERATION The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The unit shall be supplied complete with a condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 150mm diameter circular ducting. The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. Units shall be MRXBOX95-WH1 as manufactured by Nuaire. OPTIONAL SUMMER BYPASS - MRXBOX95B-WH1 The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches. When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. The bypass opens automatically when outside temperature exceeds 20ºC. This opens the damper via an actuator. Outside air supplied through the bypass is still filtered, so the air quality is optimal, irrespective of the bypass setting (open or closed). CONTROL OPTIONS The unit shall have the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), and boost speed, via inbuilt minimum and maximum speed adjustment. The fans shall have infinitely variable speed control. SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G3 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the front access panel, enabling quick and easy maintenance. The unit shall have low energy, high efficiency EC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40°C. Download specification from www.nuaire.co.uk/specifications All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Independent control of background supply and extract flow rates. • Independent control of boost speed supply and extract flow rates. • Integral fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. • Integral heat exchanger frost protection. • Discreet daily run monitor. OPTIONAL CONTROLS MRXBOX95WH-RFI Remote fail indicator. The unit shall be offered with a 5 year warranty. The manufacturer’s recommendations should be observed at all times. The unit shall be the MRXBOX95-WH1 and shall be manufactured by Nuaire. nuaire.co.uk 35 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 36 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N MRXBOX95-LOFT MECHANICAL SUPPLY & EXTRACT WITH HEAT RECOVERY UP TO 95% EFFICIENT, SAP APPENDIX Q RECOGNISED. LOFT MOUNTING DESIGN FOR SMALL TO MEDIUM HOUSES 36 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 37 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N B E NE F I T S MRXBOX95-LOFT is designed to provide optimised balanced (supply and extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas, creating comfortable well ventilated homes. MRXBOX95-LOFT uses the latest generation of low voltage DC fans and motors, counter flow heat exchanger and easy accessible controls. The heat exchanger block can recover up to 95% of the normally wasted heat. The two independent fans has full speed control for background and boost ventilation rates as well as a run-on timer facility. MEETS BUILDING REGULATIONS EXTREMELY LOW NOISE LEVELS OPTIONAL SENSORS AND DETECTORS SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. Quiet running unit ensuring occupant acceptability. Customise MRXBOX95-LOFT for enhanced performance. All supplied with pre-plugged 10m data cable and incorporates status LED. HIGH EFFICIENCY Takes the stress out of specifying. FREE OF CHARGE CODE ADVISORY SERVICE Heat exchanger is up to 95% efficient. FLEXIBLE SOLUTION EASY INSTALLATION MRXBOX95-LOFT ensures a flexible solution with four 125mm dia. and four optional 150mm dia. spigots. Compact, lightweight and simple to install. OPTIONAL SUMMER BYPASS AVAILABLE WIDE CHOICE Provides cooling during warmer months. MRXBOX95B-LOFT. Range of ducting and grilles available, please contact Nuaire. NO NEED FOR TRICKLE VENTS A cost saving and tenant acceptability. 5 YEAR WARRANTY IMPROVES INDOOR AIR QUALITY 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. Prevents condensation by keeping moisture levels low - creating a healthier environment. MRXBOX95-PIR (passive infra red) A low voltage sensor, detects movement and activates system. Incorporates overrun timer and timer adjustments. MRXBOX95-HUM A low voltage sensor, activates the system when the RH level is above set point. Incorporates overrun timer and RH setpoint level adjustment. MRXBOX95-RFI If fan failure occurs the audio visual indicator will flash a warning. LOW MAINTENANCE REQUIREMENT Filter replacement typically every 5 years. FLEXIBLE LOFT MOUNTING OPTIONS REMOVABLE G4 FILTERS Metal bracket attached to unit Washer Woodscrew A. V. mount Ceiling joist Option 1. Mounted on roof joists using four “L” shape metal brackets and AV mounts on long sides of unit. Side view example of an ‘L’ shaped fixing bracket and AV mount attached to ceiling joist. Option 2. Mounted on roof joists using four “L” shape metal brackets and AV mounts on short sides of unit. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 37 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 38 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N PERFORMANCE - MRXBOX95-LOFT Casing MRXBOX95-LOFT 300 ISO 5801 2007 AMCA 300 V 250 Type D Air Density 1.2 kg/m3 Fan Static Pressure (Pa) 200 150 Code descriptions 1 MR-XBOX95-LOFT | | | | 2 100 3 1 4 50 5 6 0 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 Air volume flow rate (l/s) 2 3 4 1. Multi-room supply and extract heat recovery 2. Product range 3. Efficiency 4. Loft application SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange effIciency % Energy Saving Trust Best Practice Performance Compliant Kitchen Plus 1 wet room 0.69 92 Yes Kitchen Plus 2 wet rooms 0.76 92 Yes Kitchen Plus 3 wet rooms 0.85 90 Yes MRXBOX95-LOFT E L E C T R I C A L & S OU N D Curve Maximum power consumption (Watts) 1 73 2 51 3 31 4 20 5 12 6 7 Hemisphical Free field dBA 38 029 2085 8200 Open inlet Open outlet Breakout Open Inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Sound Power Levels dB re 1pW 63 125 250 500 1K 2K 4K 8K dBA @3m 38 40 43 37 39 42 34 38 38 33 37 37 30 34 34 28 32 32 43 59 51 41 57 49 35 52 44 32 49 41 23 40 42 20 37 29 42 54 43 38 50 39 37 48 37 32 43 32 19 30 19 14 25 14 32 51 42 28 47 38 28 43 34 23 38 29 10 25 16 5 20 11 29 45 36 25 41 32 22 35 26 17 30 21 4 17 8 12 3 29 34 31 25 30 27 19 30 27 14 25 22 12 9 7 4 28 42 34 25 39 32 23 35 27 20 32 24 13 22 22 <10 19 <10 42 56 55 41 55 54 40 49 48 38 48 46 34 44 42 32 41 40 48 56 53 46 54 51 43 51 48 44 49 46 38 43 40 32 40 37 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving and based on SAP Appendix Q testing. Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 39 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N UNIT COMPONENTS Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. 4 optional 150mm dia. knockout spigot locations on rear of unit. If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above). G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) View from front 4 X 125mm spigots Side view (controls) 4 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top 21.5mm dia. condensate drain alternative position Side view (non controls) 21.5mm dia. condensate drain alternative position Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 39 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 40 MV H R MR XB OX95B - L O F T TEC H NI C A L I NF O R MATI O N GENERAL ARRANGEMENT OPTIONAL SUMMER BYPASS - MRXBOX95B-LOFT Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. Three optional 150mm dia. knockout spigot locations on rear of unit and one on the side (non controls). If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above) G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) Side view (controls) View from front 3 X 125mm spigots 3 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top Side view (non controls) Alternative 150mm dia. knockout spigot 21.5mm dia. condensate drain alternative position 40 029 2085 8200 21.5mm dia. condensate drain alternative position 125mm dia. spigot Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 41 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Electrical details:Voltage: 240V 1ph 50Hz Consumption: 75W (max) 0.6 Amp Fuse rating: 3 Amp NOTE: This unit must be earthed. Detail of unit control on side panel. The three core cable from the mains power supply should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. Control PCB. 24V Internal wiring Power supply PCB. 230V in, 24V dc out. Connections for optional controls Volt free relay contacts Fault Run Fan connections 230V IN 50Hz Mains SWL N Earth point L Connection to supply cord UNIT SERVING KITCHEN AND BATHROOM MAINS 230V N 50Hz L Room Fuse 2A light Light switch (Double Pole) Kitchen switch Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) UNIT SERVING KITCHEN AND TWO BATHROOMS MAINS 230V N 50Hz L Fuse 2A Light switches (Double Pole) Room lights Kitchen switch Download specification from www.nuaire.co.uk/specifications Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) nuaire.co.uk 41 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 42 MV H R MR XB OX95- L O F T TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI F I C ATION OPERATION OPTIONAL SUMMER BYPASS - MRXBOX95B-LOFT The supply and extract system shall be positioned in the loft space in accordance with the specification. The summer bypass facility during the warmer months can reduce the The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from all wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches • Optional externally interconnected sensors When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. temperature in a room by a few degrees, whilst still ventilating that room effectively. The bypass damper opens when a 230V switch signal is applied to the unit. (via a manual switch) This opens the damper via a wax actuator. When the switch signal is de-activated the unit returns to its original state (air through the heat exchanger). MRXBOX95-LOFT - CONTROL OPTIONS All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Integral speed control on supply and extract. • Integral background ventilation control/set point. • Integral boost ventilation control/set point. • Integral run on timer. • Fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. An adjustable run-on facility is integrated into the unit which allows the fans to run-on for between 1 and 60 minutes after the signals have been switched off. OPTIONAL CONTROLS The unit shall have the facility to commission the supply and extract fans via inbuilt minimum and maximum speed adjustment; the fans shall have infinitely variable speed control. MRXBOX95-LOFT - UNIT SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G4 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the top access panel, enabling quick and easy maintenance. The unit shall have low energy, high efficiency DC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40ºC. The unit shall be supplied complete with an insulated condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 150mm or 125mm circular ducting. Anti-vibration mounts are supplied with each unit to prevent vibration being tramsmitted to the ceiling timbers. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. 42 029 2085 8200 MRXBOX95-PIR Passive infra-red detector MRXBOX95-HUM Humidistat MRXBOX95-RFI Remote fail indictor Units shall be the MRXBOX95-LOFT as manufactured by Nuaire. Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 43 Breathe easy with a CPS qualification from Nuaire From 1st October 2010 domestic ventilation became ‘notifiable work’ as part of Approved Document Part F 2010 (ADF) so it is vital that installers are properly trained and qualified. As part of our commitment to installers, engineers and customers, Nuaire now offers accredited ventilation installer training at our BPEC accredited training facility. If you are an installer • learn new skills and increase your qualifications • increase the scope of work you can offer to your customers • be able to confidently install, inspect and commission domestic ventilation • minimise costs for you and your customers If you are an RSL, housebuilder or developer and subcontract installation work, recommend this course to your installers to: • ensure that all your installations are completed by qualified staff • promote sustainability, using local labour and enhance local skills with your preferred suppliers Why not benefit from Competent Persons Scheme (CPS) training at Nuaire’s BPEC approved facility? Contact your local sales representative to find out more and arrange this training. Alternatively contact our training facility on 02920 858463, e-mail [email protected] or visit www.nuaire.co.uk/cps nuaire.co.uk 43 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 44 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N MRXBOX95-LH1 MECHANICAL SUPPLY & EXTRACT WITH HEAT RECOVERY UP TO 95% EFFICIENT, SAP APPENDIX Q RECOGNISED. LOFT MOUNTING DESIGN FOR MEDIUM TO LARGE HOUSES. 44 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 45 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N B E NE F I T S MRXBOX95-LH1 is designed to provide optimised balanced (supply and extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas, creating comfortable well ventilated homes. The unit has the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), boost control will control both fans to the same volume. The heat exchanger block can recover up to 95% of the normally wasted heat. MEETS BUILDING REGULATIONS LIGHTWEIGHT SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. A one man lift for ease of install. EXTREMELY LOW NOISE LEVELS Quiet running unit, ensuring occupant acceptability. OPTIONAL REMOTE FAIL INDICATOR MRXBOX95LH-RFI is connected to the fan unit via low voltage wiring. VERY HIGH EFFICIENCY To meet customer requirements on SAP scores ensuring the reduction in emissions needed for code level 3 and above (25% reduction). CREATES A HEALTHIER ENVIRONMENT LOW MAINTENANCE DESCREET RUN MONITOR High quality components such as filters and EC motors ensure lowest possible maintenance and long life motors. Filter replacement typically every 5 years. Records units operational time. High efficiency filters removes up to 95% of dust particles. EASY TO USE Well located controls for simple installation, commissioning and use. LOW POWER CONSUMPTION Reducing operating and the life cycle costs. OPTIONAL SUMMER BYPASS AVAILABLE COMPACT Provides cooling during warmer months. MRXBOX95B-LH1. Dedicated design ensured the most compact size for duty on the market. The loft versions are specifically designed to go through the smallest loft hatches. 5 YEAR WARRANTY 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. FLEXIBLE LOFT MOUNTING OPTIONS REMOVABLE G4 FILTERS Metal bracket attached to unit Washer Woodscrew A. V. mount Ceiling joist Option 1. Mounted on roof joists using four “L” shape metal brackets and AV mounts on long sides of unit. Side view example of an ‘L’ shaped fixing bracket and AV mount attached to ceiling joist. Option 2. Mounted on roof joists using four “L” shape metal brackets and AV mounts on short sides of unit. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 45 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 46 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N PERFORMANCE - MRXBOX95-LH1 Casing MRXBOX95-LH1 500 ISO 5801 2007 AMCA 300 450 V Type D Air Density 1.2 kg/m3 400 Fan Static Pressure (Pa) 350 300 5 Code descriptions 250 4 200 MR-XBOX95-LH1 | | | | | 150 1 3 100 2 50 1 0 0 20 40 60 80 100 120 Air volume flow rate (l/s) 1. 2. 3. 4. 5. 2 3 4 5 Multi-room supply and extract heat recovery Product range Efficiency Loft application H1 = High 1 Model SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange effIciency % Energy Saving Trust Best Practice Performance Compliant Kitchen Plus 1 wet room 0.61 91 Yes Kitchen Plus 2 wet rooms 0.59 91 Yes Kitchen Plus 3 wet rooms 0.62 91 Yes Kitchen Plus 4 wet room 0.71 91 Yes Kitchen Plus 5 wet rooms 0.78 91 Yes Kitchen Plus 6 wet rooms 0.92 90 Yes MRXBOX95-LH1 E L E C T R I C A L & S OU N D Curve Maximum power consumption (Watts) 1 11 2 Sound Power Levels dB re 1pW 63 125 250 500 1K 2K 4K 8K dBA @3m Open inlet Open outlet Breakout 36 37 37 34 38 47 34 38 38 26 37 34 24 30 20 20 24 16 11 21 7 4 8 6 11 16 14 20 Open inlet Open outlet Breakout 38 43 41 35 47 47 41 47 47 29 46 42 27 39 29 23 37 31 12 30 22 12 23 21 14 25 22 3 44 Open inlet Open outlet Breakout 42 43 43 38 52 51 50 55 52 38 56 48 34 49 38 28 49 40 17 40 31 17 33 30 25 38 28 4 90 Open inlet Open outlet Breakout 43 48 45 42 56 53 55 64 55 44 64 52 42 58 44 35 58 46 22 50 37 22 40 36 32 47 35 5 160 Open inlet Open outlet Breakout 45 51 47 44 58 56 57 67 58 50 69 57 48 67 52 40 63 54 27 55 45 27 46 44 35 53 41 Hemisphical Free field dBA 46 029 2085 8200 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving and based on SAP Appendix Q testing. Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 47 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N UNIT COMPONENTS Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. 4 optional 150mm dia. knockout spigot locations on rear of unit. If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above). G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) View from front 4 X 125mm spigots Side view (controls) 4 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top 21.5mm dia. condensate drain alternative position Side view (non controls) 21.5mm dia. condensate drain alternative position Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 47 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 48 MV H R MR XB OX95B - L H 1 TEC H NI C A L I NF O R MATI O N GENERAL ARRANGEMENT OPTIONAL SUMMER BYPASS - MRXBOX95B-LH1 Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. Three optional 150mm dia. knockout spigot locations on rear of unit and one on the side (non controls). If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above) G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) Side view (controls) View from front 3 X 125mm spigots 3 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top Side view (non controls) Alternative 150mm dia. knockout spigot 21.5mm dia. condensate drain alternative position 48 029 2085 8200 21.5mm dia. condensate drain alternative position 125mm dia. spigot Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 49 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Ventilation controls Electrical details:Voltage: 240V 1ph 50Hz Consumption: LH1 - 1.3 Amp Fuse rating: 3 Amp Boost + _ For commissioning refer to user manual Continuous background + _ + _ Extract Supply Fan Fan Fan Failure NOTE: This unit must be earthed. The three core cable from the mains power supply should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. Connection to supply cord 230V IN 50Hz Mains L L N FAN 2 SUPPLY SUPPLY SWL N FAN 1 SUPPLY L N RED YEL WHI BLU RED YEL WHI BLU FAN 1 CTRL FAIL Connection to Remote Fail Indicator FAN 2 CTRL Fan Connections Detail of unit control on side panel. Speed Control Pots Fan Failure Indicator Earth point Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is pre-wired with a 2 metre fly lead. UNIT SERVING KITCHEN AND BATHROOM MAINS 230V N 50Hz L Room Fuse 2A light Light switch (Double Pole) Kitchen switch Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) UNIT SERVING KITCHEN AND TWO BATHROOMS MAINS 230V N 50Hz L Fuse 2A Light switches (Double Pole) Room lights Kitchen switch Download specification from www.nuaire.co.uk/specifications Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) nuaire.co.uk 49 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 50 MV H R MR XB OX95- L H 1 TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI F I C ATION OPERATION OPTIONAL SUMMER BYPASS - MRXBOX95B-LH1 The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The bypass damper opens when a 230V signal is applied to the unit (via a manual switch, supplied). This opens the damper via an actuator. When the switch signal is de-activated the unit returns to its original state (air through the heat exchanger). The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches. When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. The unit shall have the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), boost control will control both fans to the same volume, via inbuilt minimum and maximum speed adjustment;. The fans shall have infinitely variable speed control. MRXBOX95-LH1 - UNIT SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G4 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the top access panel, enabling quick and easy maintenance. The unit shall have low energy, high efficiency EC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40ºC. The unit shall be supplied complete with an insulated condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 150mm or 125mm circular ducting. Anti-vibration mounts are supplied with each unit to prevent vibration being transmitted to the ceiling timbers. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. 50 029 2085 8200 Outside air supplied through the bypass is still filtered, so the air quality is optimal, irrespective of the bypass setting (Open or closed). MRXBOX95-LH1 - CONTROL OPTIONS All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Independent control of background supply and extract flow rates. • Single control of boost ventilation rates • Run time monitor included • Integral Fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. OPTIONAL CONTROL MRXBOX95LH-RFI Remote fail indicator. Units shall be the MRXBOX95-LH1 as manufactured by Nuaire. Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:46 Page 51 ST YL I SH KITCHEN EXTRACT SOLUTION F O R USE WITH CENTRAL EXTRACT SYSTEM ( M E V, MVHR & CONSTANT PRESSURE) This easy to clean 60cm stainless steel cookerhood unit is fitted with two, washable metallic grease filters for quick and easy maintenance. The push button located on the front of the unit illuminates the cooking area and provides a switched live signal to trigger boost function (when linked to a Nuaire MEV, MVHR or damper system). • Extraction tube 125mm diameter ducting Metallic grease filters. • Incorporates a simple boost facility – the light switch on unit acts as trigger for boost facility • 2 metallic grease filters • 2 lights • 2 year warranty The Cookerhood does not contain a fan. Extract is via a separate fan unit e.g. MEVDC, MVHR or Constant Pressure CVD. Coding: CKRH Push button for lights and boost signal. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 51 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 52 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N MRXBOX95-LH2 MECHANICAL SUPPLY & EXTRACT WITH HEAT RECOVERY UP TO 95% EFFICIENT, SAP APPENDIX Q RECOGNISED. LOFT MOUNTING DESIGN FOR LARGER HOUSES. 52 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 53 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N B E NE F I T S MRXBOX95-LH2 is designed to provide optimised balanced (supply and extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas, creating comfortable well ventilated homes. The unit has the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), boost control will control both fans to the same volume. The heat exchanger block can recover up to 95% of the normally wasted heat. MEETS BUILDING REGULATIONS LIGHTWEIGHT SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. A one man lift for ease of install. OPTIONAL REMOTE FAIL INDICATOR Quiet running unit, ensuring occupant acceptability. MRXBOX95LH-RFI is connected to the fan unit via low voltage wiring. To meet customer requirements on SAP scores ensuring the reduction in emissions needed for code level 3 and above (25% reduction). CREATES A HEALTHIER ENVIRONMENT DISCREET RUN MONITOR High efficiency filters removes up to 95% of dust particles. Records units operational time. LOW MAINTENANCE PREVENTS CONDENSATION FROM LOFT EXTREMELY LOW NOISE LEVELS VERY HIGH EFFICIENCY High quality components such as filters and EC motors ensure lowest possible maintenance and long life motors. Filter replacement typically every 5 years. EASY TO USE Well located controls for simple installation, commissioning and use. LOW POWER CONSUMPTION OPTIONAL SUMMER BYPASS AVAILABLE Reducing operating and the life cycle costs. Provides cooling during warmer months. MRXBOX95B-LH2. COMPACT Dedicated design ensured the most compact size for duty on the market. The loft versions are specifically designed to go through the smallest loft hatches. 5 YEAR WARRANTY 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. FLEXIBLE LOFT MOUNTING OPTIONS REMOVABLE G4 FILTERS Metal bracket attached to unit Washer Woodscrew A. V. mount Ceiling joist Option 1. Mounted on roof joists using four “L” shape metal brackets and AV mounts on long sides of unit. Side view example of an ‘L’ shaped fixing bracket and AV mount attached to ceiling joist. Option 2. Mounted on roof joists using four “L” shape metal brackets and AV mounts on short sides of unit. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 53 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 54 MV H R MR XB OX95B - L H 2 TEC H NI C A L I NF O R MATI O N UNIT COMPONENTS Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. 4 optional 150mm dia. knockout spigot locations on rear of unit. If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above). G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) View from front 4 X 125mm spigots Side view (controls) 4 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top Side view (non controls) 21.5mm dia. condensate drain alternative position 54 029 2085 8200 21.5mm dia. condensate drain alternative position Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 55 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Ventilation controls Electrical details:Voltage: 240V 1ph 50Hz Consumption: LH2 - 2.2 Amp Fuse rating: 3 Amp Boost + _ For commissioning refer to user manual Continuous background + _ + _ Extract Supply Fan Fan Fan Failure NOTE: This unit must be earthed. L L N FAN 2 SUPPLY SUPPLY SWL N FAN 1 SUPPLY L N RED YEL WHI BLU RED YEL WHI BLU FAN 1 CTRL FAIL Connection to Remote Fail Indicator FAN 2 CTRL Fan Connections Connection to supply cord 230V IN 50Hz Mains Detail of unit control on side panel. The three core cable from the mains power supply should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. Speed Control Pots Fan Failure Indicator Earth point Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is pre-wired with a 2 metre fly lead. UNIT SERVING KITCHEN AND BATHROOM MAINS 230V N 50Hz L Room Fuse 2A light Light switch (Double Pole) Kitchen switch Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) UNIT SERVING KITCHEN AND TWO BATHROOMS MAINS 230V N 50Hz L Fuse 2A Light switches (Double Pole) Room lights Kitchen switch Download specification from www.nuaire.co.uk/specifications Green/yellow Blue Brown Black 3 Pole isolator Summer bypass switch Supply cord from unit Grey (only used on bypass unit) nuaire.co.uk 55 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 56 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N GENERAL ARRANGEMENT OPTIONAL SUMMER BYPASS - MRXBOX95B-LH2 Filters, PCB and Heat Exchanger Access G4 removable filter. Heat exchanger. Three optional 150mm dia. knockout spigot locations on rear of unit and one on the side (non controls). If required for use cut through the acoustic foam round the circumference of the knockout. (see figure above) G4 removable filter. Adjustment potentiometers and indication lights. Motor access. 4 x 125mm dia. spigots. Panel not removable. Illustration purposes only. DIMENSIONS (MM) Side view (controls) View from front 3 X 125mm spigots 3 alternative 150mm dia. knockout spigots on back of unit 430 Weight 21 Kg Condensate Drain 450 840 View from top Side view (non controls) Alternative 150mm dia. knockout spigot 21.5mm dia. condensate drain alternative position 56 029 2085 8200 21.5mm dia. condensate drain alternative position 125mm dia. spigot Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 57 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N PERFORMANCE - MRXBOX95-LH2 Casing MRXBOX95-LH2 700 ISO 5801 2007 AMCA 300 650 600 V 550 Type D Air Density 1.2 kg/m3 500 Fan Static Pressure (Pa) 450 400 6 Code descriptions 350 300 5 MR-XBOX95-LH2 | | | | | 250 200 4 1 150 2 3 4 5 3 100 2 50 1 0 0 20 40 60 80 100 120 140 Air volume flow rate (l/s) 1. Multi-room supply and extract heat recovery 2. Product range 3. Efficiency 4. Loft application 5. H2 = High 2 Model SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange effIciency % Energy Saving Trust Best Practice Performance Compliant Kitchen Plus 1 wet room 0.81 91 Yes Kitchen Plus 2 wet rooms 0.77 91 Yes Kitchen Plus 3 wet rooms 0.78 91 Yes Kitchen Plus 4 wet room 0.86 91 Yes Kitchen Plus 5 wet rooms 0.96 91 Yes Kitchen Plus 6 wet rooms 1.09 90 No MRXBOX95-LH2 E L E C T R IC A L & S OU N D Curve Maximum power consumption (Watts) 1 16 2 Sound Power Levels dB re 1pW 63 125 250 500 1K 2K 4K 8K dBA @3m Open inlet Open outlet Breakout 36 40 40 33 38 38 34 39 36 24 38 30 22 32 21 19 30 21 20 29 20 23 30 18 13 22 14 30 Open inlet Open outlet Breakout 40 41 41 39 49 49 41 49 46 30 49 41 28 42 31 24 41 32 21 30 21 24 33 20 18 32 24 3 62 Open inlet Open outlet Breakout 43 50 50 42 53 52 54 59 56 38 60 52 37 52 41 31 52 43 30 42 33 33 34 30 29 42 34 4 106 Open inlet Open outlet Breakout 44 50 50 46 58 57 57 65 62 43 63 55 42 58 47 37 59 50 30 50 41 33 40 36 33 47 40 5 170 Open inlet Open outlet Breakout 46 51 51 48 61 60 58 70 67 52 74 66 48 64 53 42 64 55 30 56 47 33 48 44 36 55 47 6 277 Open inlet Open outlet Breakout 50 56 56 54 65 64 62 72 69 62 77 69 55 69 60 47 69 60 39 61 52 38 54 50 43 58 51 Hemisphical Free field dBA The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving and based on SAP Appendix Q testing. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 57 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 58 MV H R MR XB OX95- L H 2 TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI F I C ATION OPERATION OPTIONAL SUMMER BYPASS - MRXBOX95B-LH2 The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The bypass damper opens when a 230V signal is applied to the unit (via a manual switch, supplied). This opens the damper via an actuator. When the switch signal is de-activated the unit returns to its original state (air through the heat exchanger). Outside air supplied through the bypass is still filtered, so the air quality is optimal, irrespective of the bypass setting (Open or closed). The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches. When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. The unit shall have the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), boost control will control both fans to the same volume, via inbuilt minimum and maximum speed adjustment;. The fans shall have infinitely variable speed control. MRXBOX95-LH2 - UNIT SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G4 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the top access panel, enabling quick and easy maintenance. The unit shall have low energy, high efficiency EC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40ºC. The unit shall be supplied complete with an insulated condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 150mm or 125mm circular ducting. Anti-vibration mounts are supplied with each unit to prevent vibration being transmitted to the ceiling timbers. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. 58 029 2085 8200 MRXBOX95-LH2 - CONTROL OPTIONS All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Independent control of background supply and extract flow rates. • Single control of boost ventilation rates • Run time monitor included • Integral Fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. OPTIONAL CONTROL MRXBOX95LH-RFI Remote fail indicator. Units shall be the MRXBOX95-LH2 as manufactured by Nuaire. Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 59 Want to find out more about building regulations and residential ventilation? You may have taken advantage of our recent CPD seminars on natural ventilation for commercial buildings but did you know Nuaire offer a wide range of CPD seminars for residential ventilation as well? So if you are working on apartments, mixed use developments or purely residential plots we can offer the right CIBSE accredited training for you, including a comprehensive guide to the domestic building regulations. New seminars from Nuaire also include: • BPEC accredited domestic installation training • Sunwarm Air (new Solar Air Pre-heat PIV category for SAP Appendix Q) • Natural ventilation • Smoke solutions • Overview of Air Handling Units Contact your local representative, email [email protected] or call 02920 858463 to organise a seminar. nuaire.co.uk 59 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 60 MV H R MR XB OX90L TEC H NI C A L I NF O R MATI O N M RX B OX 9 0 L - WHO L E HO USE HEAT RECOVERY UNIT 90% EFFICIENT, SAP APPENDIX Q RECOGNISED AND PASSIVE HOUSE CERTIFIED HEAT RECOVERY UNIT. 60 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 61 MV H R MR XB OX90L TEC H NI C A L I NF O R MATI O N B E NE F I T S MEETS REGULATIONS LOW AND EASY MAINTENANCE SAP Appendix Q recognised. Certified by Passivhaus Institut. Unit is fitted with filter indication display. Easy access to filters via “tool free” hinged door. HIGH EFFICIENCY SIMPLE TO SET UP 90% efficient, with DC motors using 50% less energy than traditional fans. Units have a display for easy installation. AUTOMATIC SUMMER BYPASS AS STANDARD EXTREMELY LOW NOISE LEVELS Acoustic insulation ensures the ideal solution for loft or cupboard installations. GUARANTEED CONSTANT AIRFLOW Unit has summer bypass as standard. Unit continuously monitors the temperature inside and outsde and will bypass the heat exchanger when appropriate. MULTI OPTION CONTROLS AND SENSORS Inbuilt controls that automatically adjust the fan speed to suit the individual systems pressure drop. Wide choice of controls including 3 speed trickle/boost and purge and optional wireless remote control. WARRANTY 5 year warranty for peace of mind. 2 self adjusting fans provide constant fresh air. HEALTHY ENVIRONMENT Removes up to 95% of the dust from the atmosphere. 1 Removable filters. Facia mounted control panel. Optional receiver. Optional wireless remote control. Download specification from www.nuaire.co.uk/specifications Speed selector switch (included). Typical installation with unit mounted in loft. nuaire.co.uk 61 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 62 MV H R MR XB OX90L TEC H NI C A L I NF O R MATI O N PERFORMANCE - MRXBOX90L Casing Air Performance of MRXBOX90L 600 0 36 72 108 144 180 216 252 288 324 360 396 (m3/hr) 432 468 ISO 5801 2007 AMCA 300 550 V Type D Air Density 1.2 kg/m3 Resistance Duct Pressure (Pa) 500 450 Code descriptions 400 MR - XBOX - 90 - L | | | | 350 300 1 250 1. 2. 3. 4. 200 150 100 Speed 1 50 10 20 26 30 40 50 60 4 Multi-room Supply and extract heat recovery Range Efficiency Size Note: Speeds 1, 2 and 3 are factory default settings and can be adjusted to suit individual requirements. 63 0 0 3 Speed 3 Speed 2 11 2 70 80 90 100 110 120 130 No. = Power consumption. Flow rate (l/s) MRXBOX90L E L E C T R I C A L , S OU N D & W E I GH T Speed 1 Code mrXbox90L Phase 1 Total motor power watts 23 Full load current amps 0.17 2 mrXbox90L 1 67 0.45 3 mrXbox90L 1 175 1.16 Breakout Supply Extract Breakout Supply Extract Breakout Supply Extract Induct Sound Power Levels dB re 1pW 63 125 250 500 1K 45 38 36 32 26 50 51 48 48 49 36 33 21 23 15 50 47 43 38 37 59 63 59 58 57 46 47 35 33 30 60 57 53 47 44 65 68 68 66 64 52 57 46 42 38 2K 18 40 7 31 52 22 43 61 34 4K 7 34 8 25 48 16 37 57 29 8K 9 23 15 22 41 16 37 52 20 Breakout dBA Weight @3m Kg 33 40 42 51 Note: Speeds 1, 2 and 3 are factory default settings and can be adjusted to suit individual requirements. MRXBOX90L View from front 165 2 = spigot to outside. Exhaust (cool stale air). 4 2 3 5 Access door 535 1 510 336 1 = spigot todwelling. Supply (warmed fresh air). 602 114 89 126 Dimensional references: 53 Bottom view 4 x 180dia spigots View from top 230 DIMENSIONS (MM) MRXBOX90L 20mm dia. 3 = spigot from dwelling. Extract (warm stale air). 4 = spigot from outside. Intake (cool fresh air). 5 = electric connections 6 = detail wall mounting (make sure to correctly place the rubber strip, washers and caps). 62 029 2085 8200 385 6 675 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 63 MV H R MR XB OX90L TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI FIC ATION OPERATION The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The unit shall have low energy, high efficiency d.c. fan/motor assemblies with sealed for life bearings, the impellers shall be forward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40ºC. The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The unit shall have integral temperature sensors that shall monitor the incoming and extracted air temperatures to provide frost protection as well as controlling the summer bypass. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: The unit shall be supplied complete with an insulated condensate drip tray and 20mm drain connection. • Manual activation from 3 position switch. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. • Optional remote RF boost switch humidity sensor. A fascia mounted control unit with microprocessor controls with LCD display enabling infinitely variable adjustment of the air volume. Via optional PCB. MRXBOX90L - CONTROL OPTIONS • Optional externally interconnected sensors. When signals are received, the fan shall alter its speed to selectable, pre-set normal and boost rates. The unit shall have the facility to commission the supply and extract fans via inbuilt minimum and maximum speed adjustment; the fans shall have infinitely variable speed control. Once the duty of the fans is set on the facia mounted controller the unit shall automatically adjust its speed to maintain the air volume flow rate selected on a constant volume principle. All versions shall have a pre-wired and factory fitted, fascia mounted multi function control panel with LCD display providing the following: • Integral speed control on supply and extract – 3 speeds available: 1. Low speed background ventilation control/set point. 2. Medium speed ventilation control/set point, for day to day boost. 3. High speed ventilation control/set point for summer boost. • Constant volume facility to adjust for system pressure. • Filter dirty & maintenance indication on fascia control. A summer bypass shall be included that shall allow fresh air to bypass the heat exchanger, when the incoming air temperature is at or above the designated “set point”. The standard warranty for MRXBOX90 series shall be for 5 years. MRXBOX90L - UNIT SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 95%. The heat exchanger shall be protected by G4 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via facia access panels, enabling quick and easy maintenance. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 63 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 64 MV H R L P XB OXDC - 2 TEC H NI C A L I NF O R MATI O N L P X B OX D C- 2 L OW P RO F I LE HEAT RECOVERY FOR APARTMENTS VERY LOW DEPTH HEAT RECOVERY UNIT WITH MULTIPLE SPIGOTS. SAP APPENDIX Q RECOGNISED. 64 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 65 MV H R L P XB OXDC - 2 TEC H NI C A L I NF O R MATI O N B E NE F I T S MEETS BUILDING REGULATIONS LOW MAINTENANCE COSTS MULTIPLE SPIGOT OPTIONS SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. Aluminium heat exchanger block and drip tray are easily accessible for quick and easy access. Easy installation position. FLEXIBLE CONDENSATE QUICK INSTALLATION VERY LOW DEPTH - WITHIN CEILING FITTING Single point bracket ideal for quick 1st and 2nd fix. Condensate drain option, either left or right hand side. 185mm, ideal forapplications where space is at a premium. HEALTHY ENVIRONMENT WARRANTY Removes up to 95% of the dust from the atmosphere. 5 year warranty for peace of mind. LOW NOISE LEVELS Acoustic lining ensures unit is ideal for applications where noise is an issue. HIGH EFFICIENCY ADVICE AND INSTALLATION SERVICE Please contact Nuaire on 02920 858 200 (or email [email protected]) for advice on ventilation solutions. Heat exchanger is up to 70% effectiveness with low energy DC motors and components help to minimise electrical energy consumed. TYPICAL INSTALLATION Ceiling Grid Mounted Supply Diffuser Ceiling Mounted Extract Grille Extract Air Fresh inlet Exhaust to outside lpXboxdc-2 in ceiling void Knockout spigots. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 65 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 66 MV H R L P XB OXDC - 2 TEC H NI C A L I NF O R MATI O N PERFORMANCE LPXBOXDC-2 DIMENSIONS (MM) LPXBOXDC LPXBOXDC-2 (m3/hr) 685mm 36 72 108 144 180 216 252 288 ISO 5801 2007 AMCA 300 450 185mm 10mm 0 V Type D Air Density 1.2 kg/m3 Fan Static Pressure (Pa) 400 850mm 350 Knockout spigots 3 x 100mm and 3 x 125mm 300 250 Code descriptions 200 3 4 75% 100% 150 LP - XBOX - DC-2 | | | 100 1 2 25% 50 50% 1 0 0 10 20 30 40 50 60 70 80 Air volume flow rate (l/s) 2 3 1. Low profile 2. Range 3. Direct current LPXBOXDC-2 E L E C T R I C A L , S OU N D & W E I GH T Ref 1 (25%) Supply fan 5 0.05 Extract fan 5 0.05 Supply fan 17 0.1 Extract fan 17 0.1 Supply fan 51 0.3 Extract fan 51 0.3 Supply fan 120 0.7 Extract fan 120 0.7 2 (50%) 3 (75%) 4 (100%) **W FLC amps Curve Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Inlet Outlet Sound figures Induct sound power level re 1pW 125 250 500 1K 2K 4K 8K 29 19 18 35 45 35 34 51 55 45 44 61 62 52 51 68 7 4 5 26 23 12 9 42 33 22 19 52 40 29 26 59 2 4 5 16 15 9 9 32 25 19 19 42 32 26 26 49 31 26 26 39 47 42 42 55 57 52 52 65 64 59 59 72 28 23 17 43 44 39 33 59 54 49 43 69 61 56 50 76 15 14 7 34 31 30 23 50 41 40 33 60 48 47 40 67 16 8 4 34 32 24 19 50 42 34 29 60 49 41 36 67 Breakout Weight dBA @3m Kg 15 25 15 29 38 44 *Fans are programmed with a soft start, therefore starting current is the same as the FLC. Please note step curves shown are for information purposes only and are not individual units. The units actual duty range is infinitely variable. **W = Watts are total power consumption. S A P A PPE N DI X Q T E S T R E S U LT S Application Specific fan power Heat exchange efficiency Energy Savign Trust Best Practice (W/l/s) (%) Performance Compliant Kitchen + 1 wetroom 0.80 66 No Kitchen + 2 wetrooms 0.76 65 No Kitchen + 3 wetrooms 0.79 64 No Kitchen + 4 wetrooms 0.89 62 No Kitchen + 5 wetrooms 1.04 61 No Kitchen + 6 wetrooms 1.37 60 No Kitchen + 7 wetrooms 1.69 59 No 66 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 67 MV H R L P XB OXDC - 2 TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI FIC ATION OPERATION LPXBOXDC-2 CONTROL OPTIONS The supply and extract ventilation unit shall be as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The ventilation unit shall automatically vary the ventilation rate, as it receives signals from one of the optional interconnected sensors. When signals are received, the fan shall either vary its speed proportionally or on a trickle and boost principle. The unit shall have the facility to commission the supply and extract fans individually via inbuilt minimum and maximum speed adjustment, the fans themselves shall have infinitely variable speed control. All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Integral speed control on supply and extract. • Integral background ventilation control/set point. • Integral boost ventilation control/set point. • Integral run on timer. • Volt free failure indication (direct from individual fan). • Integral S/L terminal for boost from remote switch, e.g. light switch. LPXBOXDC-2 UNIT SPECIFICATION The fans shall be acoustically lined with high density class “O” flame retardant insulation, giving extremely low noise levels. The unit shall have a heat exchanger block manufactured from aluminium with a thermal efficiency of approximately 70% which shall be protected by G2 grade filters on supply and extract. It shall come complete with a condensate drip tray and 22mm drain connection, integral minimum and maximum speed controls, run on timer and facia mounted failure indication. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and as detailed in the ventilation equipment schedule. The unit shall have low energy, high efficiency d.c. fan/motor assemblies with sealed for life bearings. The depth of the low profile unit shall not be greater than 185mm and shall incorporate a low profile single point mounting bracket, (allow 10mm for bracket). The unit shall be constructed with one removable panel allowing full maintenance access to all components. To facilitate the interconnection of branch ducts the unit shall have multiple spigot connections with integrated balancing dampers. Spigot connections provided. Download specification from www.nuaire.co.uk/specifications Units shall be the LPXBOXDC-2 as manufactured by Nuaire. The standard warranty for LPXBOXDC series shall be for 5 years. nuaire.co.uk 67 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 68 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N CO O KE RX B OX - KI T CHE N C ANOPY HEAT RECOVERY SYSTEM SPACE SAVING ABOVE COOKER HEAT RECOVERY UNIT WITH INTEGRAL AUTOMATIC BOOST. 650mm minimum 68 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 69 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N B E NE F I T S SLIM LINE PROFILE FLEXIBLE INSTALLATION ADVICE AND INSTALLATION SERVICE Designed to sit behind cupboard door. Connections are either from the sides or top. Side connections are used to enable the ducting to run across the top of kitchen wall units. Please contact Nuaire on 02920 858 200 (or email [email protected]) for advice on ventilation solutions and installation service. QUICK & EASY MAINTENANCE WARRANTY Front and underneath panels allows for quick access to condensate drain and electrical supply, with washable grease filters. 5 year warranty for peace of mind. HEAT RECOVERY From 66% effective. Recovers heat when cooking, supplying warm air into dwelling avoiding condensation. MEETS REGULATIONS New build ‘best practice’ rating in GPG 268. FINISH FLEXIBLE SPEED CONTROL White pre-coated steel finish with white ABS spigot connections. 4 speed settings with automatic boost facility (thermostat senses air temp and boosts when required). TYPICAL INSTALLATION Alternative spigot postion. Air supply to home Supply air from outside Extract from bathroom en-suite Grease filter Exhaust air to outside Extract flow above hob Designed to sit behind the cupboard door. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 69 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 70 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N PERFORMANCE - COOKERXBOX Casing COOKERXBOX Supply Fan 0 3 (m /hr) 36 72 108 144 180 216 300 ISO 5801 2007 AMCA 300 250 Type D Air Density 1.2 kg/m3 Fan Static Pressure (Pa) V 200 150 100 Boost 3 50 1 0 5 4 0 2 10 20 30 40 50 60 Code Air volume flow rate (l/s) CKR XBOX COOKERXBOX Extract Fan 0 36 (m3/hr) 72 108 144 180 216 ISO 5801 2007 AMCA 300 300 V Fan Static Pressure (Pa) 250 Type D Air Density 1.2 kg/m3 200 150 Boost 100 4 5 50 1 0 0 2 10 3 20 30 40 50 60 Air volume flow rate (l/s) B Access panels In order to make connections for the condensate drain and electrical supply the access panels shown should be removed, starting with No.1. All panels should be stored safely to avoid damage. A = Supply air to house. 3 A Fixing holes 1 D 2 C B = Extract air from bathroom/ensuite. C = Exhaust air to outside. D = Supply air from outside. 4 70 029 2085 8200 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 71 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N COOKERXBOX E L E C T R IC A L , S OU N D & W E I GH T Phase Motor power kW Full load* current amps 1 60 0.260 4 34 3 24 2 1 Extract Fan Curve Code 5 ckrXbox Induct Sound Power Levels dB re 1pW 63 125 250 500 1K 2K 4K 8K Breakout dBA Weight @3m Kg Boost open inlet 58 60 62 53 47 45 40 30 39 0.140 Speed 4 open inlet 52 54 55 46 40 38 29 26 31 0.105 Speed 3 open inlet 49 51 43 40 34 30 24 25 24 18 0.080 Speed 2 open inlet 48 51 39 35 30 25 22 20 21 12 0.060 Speed 1 open inlet 44 45 37 32 27 23 22 20 18 20 Supply Fan 5 60 0.260 Boost open outlet 51 63 71 66 65 61 54 44 52 4 ckrXbox 1 37 0.140 Speed 4 open outlet 48 52 64 61 59 54 45 36 46 3 24 0.105 Speed 3 open outlet 44 50 53 54 53 47 35 28 39 2 18 0.080 Speed 2 open outlet 38 39 41 41 39 27 22 20 25 1 12 0.060 Speed 1 open outlet 38 39 37 32 27 23 22 20 17 Note: Part L1 compliance: Specific Fan Power (SFP) will be less than 2.0 for typical system resistances (estimated at 75Pa for boost condition), at default speeds (1 and 3). Minimum heat exchanger efficiency at all settings is 66%. *Unit has a soft start function therefore the starting current is same as flc. DIMENSIONS (MM) COOKERXBOX View from bottom View from front View from side Electrical supply inlet 25 25 100 dia. 25 65 100 dia. 200 79 500 563 22mm dia. 127.5 538 538 Condensate connection 89 595mm Download specification from www.nuaire.co.uk/specifications 295mm nuaire.co.uk 71 Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 72 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N DUCTING CONNECTIONS TOP SPIGOT FUNCTIONS There are four ducting connections to be made from the sides of the unit. The four ducting positions on the top of the unit can be employed for other installation options. For optional installation choice. The numbered spigots perform the same function as the equivalent numbered side spigots. SIDE SPIGOT FUNCTIONS 1) Fresh air input to unit (100mm dia). 4 2) Exhaust air to outside (100mm dia). 3 3) Fresh air supply to dwelling (100mm dia). This duct should terminate via a discharge diffuser located centrally within the dwelling. 1 4) Extract air from bathroom/en-suite (100mm dia). 2 Note: the distance between the underside of the unit and the supporting surface for the cooking vessel must be at least 650mm. WIRING - COOKERXBOX Circuit board connections. GRN BLK BRN BLU GRN SUPPLY FAN N Room light BLK L N BRN L EXTRACT FAN 230V 1ph 50Hz supply 3 pole fan isolator BLU Fuse 3 amp SL Aux switch(es) (optional) SUPPLY SPEED 2 1 EXTRACT SPEED SETPOINT 1 26 28 30 2 3 3 24 22 4 4 Operation 42 TEMP SENSOR B LIVE L NEUTRAL N EARTH SW LIVE Fan Speeds Unless onsite conditions dictate otherwise both supply and extract fans should be set on the lowest setting. Boost Set Point Boost should be triggered whilst cooking. It is suggested the set point should be set to 32oC although this may need changing depending on the user lifestyle. Connecting Auxillary Switches It is possible to provide additional control of the unit by means of up to two auxilliary switches connected to the switched live. These switches may be operated manually or by additional Thermostats, Humidistats and PIR Detectors. 72 SUPPLY B A Boost Fan/s Selection By default only the extract fan boosts to full speed. To change this to boost the supply fan as well as the extract fan, move link to position B. 029 2085 8200 40 A The unit is designed to continuously supply and extract air. The unit contains a thermostat to sense the extract air temperature. When the temperature exceeds the boost set point the extract fan boosts to full speed. Boost speed may also be activated by remote switch/es. Ensure that supply/extract motor wires are swapped over if opposite hand is required. 32 34 36 38 SL Nuaire Residential MVHR 1_Layout 1 12/08/2011 10:47 Page 73 MV H R C O O K ER B OX TEC H NI C A L I NF O R MATI O N CO NSULTA NT S SP E CI FIC ATION OPERATION Whole home ventilation unit with heat recovery for homes without a loft. COOKERXBOX - UNIT SPECIFICATION The casing shall be manufactured from easy to clean pre-coated galvanised steel. A washable flame retardant supply air filter of G3 grade shall be fitted which may be accessed behind the grease filters. The unit shall incorporate two backward curved centrifugal impeller fans for continuous central input and demand activated multiple extract from ‘wet’ areas. The fans shall be driven directly by high efficiency AC motors with a maximum power consumption of 60 watts each. The unit shall incorporate an easily removable, washable plate heat exchanger manufactured in flame retardant aluminium. The heat exchanger shall be arranged to remove heat from the extract airflow and to transfer it to the input airflow whilst permitting no mixing. Up to 66% of the available heat may be recovered. The unit shall incorporate an integral grille with washable grease filters and may be configured for general kitchen extract or for above hob application. The unit input fan volume control setting shall be adjustable via an integral 4 position switch and shall typically provide 14-33l/s continuously with the facility to boost, if required to 47l/s with the extract boost. The unit extract fan shall operate continuously at a low background rate, typically 15-37l/s, set via an integral 4 position switch, boosting to high duty extract of approximately 47l/s when integral sensor detects available heat in the extract air stream. Alternatively, high duty extract may be via a separate switch (not supplied). The standard warranty for cookerXbox shall be for 5 years. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 73 MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION MRXBOX95B-LP1 MECHANICAL SUPPLY & EXTRACT WITH HEAT RECOVERY VERY LOW DEPTH CEILING VOID HEAT RECOVERY UNIT SAP APPENDIX Q ELIGIBLE. 1 029 2085 8200 MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION BENEFITS MRXBOX95B-LP1 is specifically designed for apartment applications where there are ceiling void limitations. The MVHR unit provides optimised balanced (supply & extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas, creating comfortable well ventilated homes. The unit has a facility to commission the supply & extract fans independently on both minimum and maximum speeds. MEETS BUILDING REGULATIONS IMPROVES INDOOR AIR QUALITY SIMPLE FAN CONTROLS SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. High efficiency filters helps to create a healthy living environment. Independent controls for supply & extract for quick and easy commissioning. PROVIDES EXTRA STORAGE/CUPBOARD SPACE NO REQUIREMENT FOR TRICKLE VENTS OPTIMUM PERFORMANCE Low Specific Fan power and high efficiency results in SAP Q. EXTREMELY LOW NOISE LEVELS Quiet running unit ensuring occupant acceptability. OVERCOMES VALUABLE CUPBOARD SPACE RESTRICTIONS Occupant acceptability. Reduces noise from outside - overcomes draught issues. LOW & EASY MAINTENANCE 5 YEAR WARRANTY Easy accessible filters on underneath cover via loft hatch. 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. INTEGRAL FROST PROTECTION Protects the unit during extreme cold spells. Mounted within ceiling void. DISCREET RUN MONITOR ADDED SECURITY Windows may be kept closed. INSTALLATION FEATURE TYPICAL INSTALLATION Air valve in ceiling. 204 x 60mm ducting in ceiling void. Side view of unit mounted in the ceiling void. Access to second filter Typical side view example of a unit mounted in a ceiling void using 204 x 60mm rectangular ducting and air valves. Download specification from www.nuaire.co.uk/specifications Filter plate and filter being removed Control module Removeable filters without removing the unit cover. nuaire.co.uk 2 MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION Casing PERFORMANCE MRXBOX95B-LP1 550 ISO 5801 2007 AMCA 300 500 V Type D Air Density 1.2 kg/m3 450 Fan Static Pressure (Pa) 400 1 350 Code description 300 2 MR-XBOX95-B-LP1 | | | | 250 200 3 150 1 4 100 50 5 0 0 5 10.0 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 Air volume flow rate (l/s) 2 3 4 1. Multi-room supply and extract heat recovery 2. Product range 3. Bypass 4. Low profile MRXBOX95B-LP1 ELECTRIC AL & SOUND Curve 1 Maximum power consumption (Watts) 100 2 85 3 65 4 45 5 26 Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open Inlet Open outlet Breakout Sound Power Levels dB re 1pW 63 125 250 50 56 55 57 67 68 64 64 63 50 52 55 56 63 65 62 62 61 45 47 48 52 57 58 57 56 54 39 42 37 46 50 49 50 49 44 36 36 26 39 43 37 42 40 33 500 55 69 62 51 65 57 44 58 49 34 49 39 24 38 27 1K 46 67 52 43 63 48 35 56 41 26 46 29 17 35 14 2K 42 65 47 39 59 43 30 53 33 19 44 19 14 28 - 4K 32 56 38 27 51 32 20 42 23 12 30 14 17 - 8K 23 48 30 17 42 20 9 32 21 10 - dBA @3m 43 40 33 23 12 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving based on SAP Appendix Q testing. Please note step curves shown are for information purposes only and are not individual units. The units actual duty range is infinitely variable. SAP APPENDIX Q TEST RESULTS Exhaust terminal Configuration Fan speed setting Specific fan power (W/l/s) Heat exchange efficiency % Exhaust terminal Configuration Fan speed setting Specific fan power (W/l/s) Heat exchange efficiency % Kitchen + 1 wet room 100% variable 0.54 75 Kitchen + 5 wet rooms 100% variable 0.95 78 Kitchen + 2 wet rooms 100% variable 0.60 76 Kitchen + 6 wet rooms 100% variable 1.14 79 Kitchen + 3 wet rooms 100% variable 0.69 77 Kitchen + 4 wet rooms 100% variable 0.79 78 3 029 2085 8200 MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION GENERAL ARRANGEMENT MRXBOX95B-LP1 Control module 4 x Spigots for 204 x 60mm rectangular ducting Filter and filter plate being removed Second filter and filter plate being removed MRXBOX95B-LP1 - DIMENSIONS (mm) View from underside with lid removed (B) View from top with lid (A) 900 668 hole centres 371 700 885 hole centres 21.5mm condensate drain View from control side (A) End view 200 67 153 740 (Filter access distance) 850 (B) Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 4 MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. Control module The unit is supplied with a flexible cord for connection to the mains supply. Electrical details:Voltage: 240V 1ph 50Hz Consumption: LP1 - 1.3 Amp Fuse rating: 3 Amp NOTE: This unit must be earthed. The three core cable from the mains power supply should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. Detail of unit control on control panel. Tamper proof label following commissioning. B R N B R N EXTRACTFAN FAN EXTRACT SUPPLY FAN B L U SWL EXTRACT SUPPLY B L U BYPASS BLU WHI YEL RED SUPPLY YEL WHI BLU RED FAIL 3 Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is pre-wired with a 2 metre fly lead. 2 Connection to Remote Fail Indicator Ref: MRXBOX95LH-RFI UNIT SERVING KITCHEN AND BATHROOM Supply cord from unit MAINS 230V N 50Hz L Fuse 2A Light switch (Double Pole) Room light Blue Brown Black 3 Pole isolator Kitchen switch UNIT SERVING KITCHEN AND TWO BATHROOMS Green/yellow Blue Brown Black MAINS 230V N 50Hz L Fuse 2A Room lights Light switches (Double Pole) Kitchen switch 5 029 2085 8200 3 Pole isolator Supply cord from unit MVHR MRXBOX95B-LP1 TECHNIC AL INFORMATION CONSULTA NTS SPECIFIC ATION OPERATION The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches. When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. The unit shall have the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), and boost speed, via inbuilt minimum and maximum speed adjustment. The fans shall have infinitely variable speed control. SPECIFICATION The unit shall be manufactured from galvanised sheet steel with a white, pre-painted removable access panel. The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate, aluminium, counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 80%. The heat exchanger shall be protected by G3 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the underside access panels, enabling quick and easy maintenance. The unit shall have low energy, high efficiency EC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40°C. Motor assemblies shall be removable from the underside of the unit and will not require the unit to be removed from situ. The unit shall be supplied complete with a condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 204x60mm rectangular ducting. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. Units shall be MRXBOX95B-LP1 as manufactured by Nuaire. The unit shall be fitted with 100% summer bypass as standard. The bypass opens automatically when outside temperature exceeds 20 Deg.C. This shall open the damper via an actuator. Outside air supplied through the bypass shall be filtered, so the air quality is optimal, irrespective of the bypass setting (open or closed). The unit shall be offered with a 5 year warranty CONTROL OPTIONS All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Independent control of background supply and extract flow rates. • Independent control of boost speed supply and extract flow rates. • Integral fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. • Integral heat exchanger frost protection. • Discreet daily run monitor. OPTIONAL CONTROLS The unit shall have a maximum depth of 200mm to fit within ceiling void restrictions. Download specification from www.nuaire.co.uk/specifications MRXBOX95WH-RFI 230-PIR HUMISEN 773532 Remote fail indicator. PIR Sensor with run-on timer. 230V Humidistat. Normal/boost switch. nuaire.co.uk 6 MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION MRXBOX95-WM2 MECHANIC AL VENTILATION WITH HEAT RECOVERY UP TO 90% EFFICIENT, SAP APPENDIX Q RECOGNISED. WALL/CUPBOAD MOUNTING DESIGN FOR MEDIUM SIZED HOUSES & APARTMENTS. 1 029 2085 8200 MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION BENEFITS MRXBOX95-WM2 is designed to provide optimised balanced (supply & extract) mechanical ventilation with heat recovery. Tempered air is delivered into ‘living’ areas whilst extracting moisture laden air from ‘wet’ areas creating comfortable well ventilated homes. The unit has the facility to commission the supply & extract fans independently on both minimum and maximum speeds. The heat exchanger block can recover up to 90% of normally wasted heat. MEETS BUILDING REGULATIONS ADDED SECURITY SAP Appendix Q recognised. Part F&L - England & Wales. Scottish technical handbook (BRE398 referenced). Technical booklet K1998. Windows may be kept closed. PRE-COMMISSIONING FILTER PROTECTION IMPROVES INDOOR AIR QUALITY OPTIMUM PERFORMANCE High efficiency filters helps to create a healthy living environment. Low Specific Fan power and high efficiency results in SAP Q. LOW & EASY MAINTENANCE SUITABLE FOR MEDIUM SIZE APPLICATIONS Easy accessible filters from front cover – no tools required. Filter replacement typically every 12 - 18 months. Designed to meet the duty for average, medium size properties. DESCREET RUN MONITOR Filters are covered in a removable protective film to prevent clogged up filters prior to occupant handover. SIMPLE FAN CONTROLS Independent controls for supply & extract for quick and easy commissioning. NO REQUIREMENT FOR TRICKLEVENTS Reduces noise from outside - overcome draught issues. Records units operational time. COMPACT The unit fits easily into cupboards not taking up valuable storage space. 5 YEAR WARRANTY INTEGRAL FROST PROTECTION Protects the unit during extreme cold spells. 5 year parts and 1 year labour warranty guarantee reduced life costs and peace of mind. EXTREMELY LOW NOISE LEVELS Quiet running unit ensuring occupant acceptability. INSTALLATION FEATURES Filter being removed Filter cover Typical cupboard installation of MRXBOX95-WM2. Download specification from www.nuaire.co.uk/specifications Removeable filters without removing front cover. nuaire.co.uk 2 MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION Casing PERFORMANCE MRXBOX95-WM2 550 ISO 5801 2007 AMCA 300 500 V Type D Air Density 1.2 kg/m3 450 1 Fan Static Pressure (Pa) 400 350 Code description 300 MR-XBOX95-WM2 | | | | 2 250 1 200 3 4 50 3 4 1. Multi-room supply and extract heat recovery 2. XBOX95 product range 3. Wall/cupboard application 4. Medium duty 150 100 2 5 0 0 10 20 30 40 50 60 70 80 90 100 110 120 Air volume flow rate (l/s) MRXBOX95-WM2 ELECTRIC AL & SOUND Curve 1 Maximum power consumption (Watts) 150 2 75 3 36 4 14 5 8 Sound Power Levels dB re 1pW 63 125 250 57 57 61 55 65 71 61 61 56 51 51 55 53 59 61 56 55 51 48 48 48 52 56 55 52 54 47 44 44 39 51 52 49 49 52 44 40 39 25 50 48 41 46 50 39 Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open inlet Open outlet Breakout Open Inlet Open outlet Breakout 500 56 67 53 48 58 44 42 53 39 34 48 34 22 41 27 1K 50 64 47 40 55 38 33 49 33 27 43 29 18 36 22 2K 47 60 44 35 52 35 28 45 30 21 37 25 <16 24 19 4K 36 51 35 25 39 23 18 32 <16 <16 25 <16 <16 17 <16 8K 34 43 33 20 32 17 <16 25 <16 <16 18 <16 <16 <16 <16 dBA @3m 40 52 37 32 43 29 26 37 26 18 31 22 <16 24 18 The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking into account any heat recovery saving based on SAP Appendix Q testing. SAP APPENDIX Q TEST RESULTS Application Specific fan power (W/l/s) Heat exchange efficiency % Energy Saving Trust Best Practice Compliant Application Specific fan power (W/l/s) Heat exchange efficiency % Energy Saving Trust Best Practice Compliant Kitchen Plus 1 wet room 0.54 89 Yes Kitchen + 4 wet rooms 0.73 86 Yes Kitchen Plus 2 wet rooms 0.54 87 Yes Kitchen + 5 wet rooms 0.87 86 Yes Kitchen Plus 3 wet rooms 0.62 87 Yes 3 029 2085 8200 MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION GENERAL ARRANGEMENT MRXBOX95-WM2 Mounting bracket on wall and rear of unit. 4 1 3 2 Two removable G3 filters. Condensate tray. SPIGOT LOCATION & DUCTING REFERENCES Spigot 1. Spigot 2. Spigot 3. Spigot 4. 125mm dia. = extract air from dwelling. 125mm dia. = exhaust air to outside. 125mm dia. = intake air from outside. 125mm dia. = supply air to house. MRXBOX95-WM2 - DIMENSIONS (mm) Mounting bracket Side view View from top 419 503 172 172 90 Front view Spigots 4 x 125mm dia. 603 Download specification from www.nuaire.co.uk/specifications 353 nuaire.co.uk 4 MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION ELECTRICAL CONNECTION Please note: the electrical connection of the unit must be be carried out by a qualified electrician. The unit is supplied with a flexible cord for connection to the mains supply. Electrical details:240V 1ph 50Hz Consumption: WM2 - 1.3 Amp Fuse rating: 3 Amp NOTE: This unit must be earthed. Detail of unit control on front panel. Tamper proof label following commissioning. The mains power supply cable should be connected to a fixed wiring installation, via a fused isolator, in accordance with current IEE wiring regulations. B L U Voltage: B R N B R N EXTRACT FAN SWL EXTRACT SUPPLY SUPPLY FAN B L U BYPASS BLU WHI YEL RED SUPPLY YEL WHI BLU RED FAIL Note: Wiring is for reference purposes only as the connections above are factory fitted. The unit is pre-wired with a 2 metre fly lead. UNIT SERVING KITCHEN AND BATHROOM Supply cord from unit MAINS 230V N 50Hz L Fuse 2A Light switch (Double Pole) Room light Blue Brown Black 3 Pole isolator Kitchen switch UNIT SERVING KITCHEN AND TWO BATHROOMS Green/yellow Blue Brown Black MAINS 230V N 50Hz L Fuse 2A Room lights Light switches (Double Pole) Kitchen switch 5 029 2085 8200 3 Pole isolator Supply cord from unit MVHR MRXBOX95-WM2 TECHNIC AL INFORMATION CONSULTA NTS SPECIFIC ATION OPERATION The supply and extract ventilation unit shall be positioned as indicated on the drawings and shall be in accordance with the particular fan schedule in the specification. The unit shall be supplied complete with a condensate drip tray and 21.5mm drain connection. The unit shall be suitable for 125mm diameter circular ducting. The combined supply and extract with heat recovery unit, shall supply filtered fresh air to each of the habitable rooms and vitiated air shall be extracted from the wet areas e.g. bathroom, en-suite, w.c, kitchen, utility rooms, etc. The supply air shall be pre-heated by the warm extract air via the integrated counter-flow heat exchanger element. The extracted air shall also be filtered before it reaches the heat exchanger block. The breakout noise level and power requirements shall be as detailed by the unit manufacturer and in accordance with the ventilation equipment schedule. Units shall be MRXBOX95-WM2 as manufactured by Nuaire. CONTROL OPTIONS The ventilation unit shall vary its speed and therefore the ventilation rate, as it receives signals from one of the following: • Switched live signal from light / remote switches. When signals are received, the fan shall alter its speed to adjustable, normal and boost rates. The unit shall have the facility to commission the supply and extract fans independently on minimum speed (continuous background ventilation), and boost speed, via inbuilt minimum and maximum speed adjustment. The fans shall have infinitely variable speed control. All versions shall have the following functions integrally mounted within the fan unit on a purpose made PCB, all such components pre-wired and factory fitted by the manufacturer: • Independent control of background supply and extract flow rates. • Independent control of boost speed supply and extract flow rates. • Integral fan failure indication. • Integral S/L terminal for boost from remote switch, e.g. light switch. • Integral heat exchanger frost protection. • Discreet daily run monitor. OPTIONAL CONTROLS MRXBOX95WH-RFI Remote fail indicator. SPECIFICATION The unit shall be fully insulated providing excellent thermal and acoustic characteristics and shall be complete with a multi plate counter flow high efficiency heat exchanger block, with a thermal efficiency of up to 90%. The heat exchanger shall be protected by G3 grade filters on fresh air inlet and system extract. The heat exchanger and filters shall be accessible via the front access panel, enabling quick and easy maintenance. The unit shall be offered with a 5 year warranty. The manufacturer’s recommendations should be observed at all times. The unit shall be the MRXBOX95-WM2 and shall be manufactured by Nuaire. The unit shall have low energy, high efficiency EC fan/motor assemblies with sealed for life bearings, the impellers shall be backward curved centrifugal type. The motors shall be suitable of an ambient temperature of 40°C. Download specification from www.nuaire.co.uk/specifications nuaire.co.uk 6