Download Gauger420 User Manual - SOLID APPLIED TECHNOLOGIES LTD
Transcript
$RAT 3 $ $TMP 3 $ $SNS 0 $ $CYLV 5.0 , 2.0 $ Tracking rate is 10 meters per minute Temperature unit is Celsius Temperature sensor is the internal Tank is vertical cylindrical, height 5m and diameter 2m $TWOW 0.0 , 15700 , 20 , 2 , 1 $ 4mA represents 0 liters, 20mA represents 15700 liters, error is represented by 22mA V.6.4 OCF – Flow Mapping Table example (American Units) $RSD $ Reset to factory defaults $UNT 2 $ Unit system is American $EMP 3.5 $ Empty level is 3.5 feet $TBL 1, 0, 0 $ $TBL 2, 10, 110.8 $ Four mapping points are defined for table. 0 level is mapped to 0 $TBL 3, 20, 150 $ flow, level of 10 is mapped to flow 110.8, level of 20 is mapped to $TBL 4, 25, 255.0 $ flow 150. Level and Flow units are defined in the command OCF. $OCF 10, 1, 4, 3$ Calculate flow using four entries of table. The table defines Level in inches and flow in Liter/Sec. Note: Always verify then re-verify that your basic settings are correct including distance to empty level, distance to full level, level or distance choice. Most wrong readings originate from incorrect setup. ______________________________________________________________________________ Gauger420 – User Manual page 62 of 126 May 2014 Rev 2.04