Download - AD INSTRUMENTS
Transcript
Multifunction Tester User Manual Function Button Description BUTTON 1 2 AUTO RCD tΔ F1 30mA 100mA F2 AC G AC S F3 0 F4 180 3 4 5 RCD IΔN 300mA 500mA 650mA DC G DC S 6 7 1A 10mA G: General (non-delayed) RCDs S: Selective (time-delayed) RCDs Possible setup ratios depending on the RCD Trip Current X X1/2 X1 X2 X5 AUTO RAMP 10mA O O O O O O 30mA O O O O O O 100mA O O O O O O 300mA O O O X X O 500mA O O O X X O 650mA O O X X X O 1A O O X X X X Maximum measurement Trip Time of the RCD (Complying to BS 61008 and 61009) ½XIΔN V 2xIΔN 5xIΔN IΔN tΔ= General tΔ= tΔ= Max.40mS tΔ= (non-delayed) Max.1999mS Max.500mS Max.150mS RCD tΔ= Selective tΔ= tΔ= Max.40mS tΔ= (time-delayed) Max.1999mS Max.500mS Max.150mS RCDs IΔN: Trip-Out Current tΔ: Trip-Out Time : Indicates that the thermal protection device has operated and therefore cannot make any measurements. Instrument must be allowed to cool for a period before tests can continue. 21