Transcript
PIX 9 Withdrawable 12 kV voltage transformers, with removable fuses (contd.) 8 ■■ Remove the removable floor. ■■ Dismantle: □□ the 3 lateral fixing screws on the front and on each side, □□ the wiring connector mask (8). ■■ Extract the casing. ■■ Access to the cables is now possible. Before dismantling, note the position of the connections. They must be slightly inclined towards the interior of the compartment. 9.7 Refitting the casing Proceed with remounting operations, in the reverse order to those described for dismantling. AMTNoT077-02 21