Download SYSMAC CJ Series CJ2 CPU Unit Hardware User`s Manual

Transcript
5 Installation
5-3-6
Connecting I/O Devices
Input Devices
Use the following information for reference when selecting or connecting input devices.
z DC Input Units
The following types of DC input devices can be connected.
Contact output
IN
DC Input Unit
COM
IN
Sensor
Power
Supply
5-3 Wiring
Two-wire DC output
DC Input Unit
COM
5
IN
Output
7 mA
5-3-6 Connecting I/O Devices
NPN open-collector output
Sensor
Power
Supply
DC Input Unit
COM
0V
NPN current output
Current
regulator
DC Input Unit
Output
IN
7 mA Sensor
Power
0 V Supply
COM
PNP current output
Sensor
Power
Supply
Output
7 mA
0V
DC Input Unit
IN
COM
Voltage output
COM
Output
IN
DC Input Unit
0 V Sensor
Power
Supply
• The circuit below should NOT be used for I/O devices having a voltage output.
Voltage output
Sensor
Power
Supply
Output
0V
CJ2 CPU Unit Hardware User’s Manual
DC Input Unit
IN
COM
5-35