Chapter 9: Events and alarms U min [V]: Minimum battery voltage threshold. An alarm is generated if the voltage 7.3.4 measured on the battery is lower than this. Default value: 10Volts. U nom [V]: The battery nominal voltage. Possible choices are 2V, 6V and 12V. Default value: 12V. Capacity [Ah]: The battery nominal capacity as specified by its datasheet. Default value: 100Ah. Ri nom [mΩ]: The nominal battery internal resistance as specified by the battery’s vendor datasheet. This is a reference only and may differ from the values measured by the system. Default value: 10mΩ. Discharge cycles: The maximum charge-discharge cycles the battery can withstand as specified by its datasheet. Default value: 500. Life span: The maximum life span (expressed in h) the battery can withstand as specified by its datasheet. Default value: 60000. T max [°C]: Maximum battery temperature threshold. An alarm is generated if the temperature measured on the battery is exceeding this value. Default value: 50. T min [°C]: Minimum battery temperature threshold. An alarm is generated if the temperature measured on the battery is lower than this value. Default value: 0. CU configuration 12. Select the CU as shown on Figure 24. Figure 24: CU configuration 13. Fill in the following fields (strings and batteries count are automatically updated read only fields): Radio channel: Choose the desired RF channel for the system. If more than one BATTMASTER® system is installed on the same location the user must select a different channel for each system to avoid interference between them. Default value: channel 1. Acquisition interval [minutes]: The interval between 2 DAM/IDAM measurements acquisitions. Default value: 60minutes. Ri sample interval [hours]: The interval between 2 batteries internal resistance measurements. Default value: 24hours. BATTMASTER® user manual rev. 9 Page 21/49