Chapter 9: Events and alarms
 U min [V]: Minimum battery voltage threshold. An alarm is generated if the voltage







7.3.4
measured on the battery is lower than this. Default value: 10Volts.
U nom [V]: The battery nominal voltage. Possible choices are 2V, 6V and 12V. Default
value: 12V.
Capacity [Ah]: The battery nominal capacity as specified by its datasheet. Default value:
100Ah.
Ri nom [mΩ]: The nominal battery internal resistance as specified by the battery’s vendor
datasheet. This is a reference only and may differ from the values measured by the
system. Default value: 10mΩ.
Discharge cycles: The maximum charge-discharge cycles the battery can withstand as
specified by its datasheet. Default value: 500.
Life span: The maximum life span (expressed in h) the battery can withstand as specified
by its datasheet. Default value: 60000.
T max [°C]: Maximum battery temperature threshold. An alarm is generated if the
temperature measured on the battery is exceeding this value. Default value: 50.
T min [°C]: Minimum battery temperature threshold. An alarm is generated if the
temperature measured on the battery is lower than this value. Default value: 0.
CU configuration
12. Select the CU as shown on Figure 24.
Figure 24: CU configuration
13. Fill in the following fields (strings and batteries count are automatically updated read only
fields):
 Radio channel: Choose the desired RF channel for the system. If more than one
BATTMASTER® system is installed on the same location the user must select a different
channel for each system to avoid interference between them. Default value: channel 1.
 Acquisition interval [minutes]: The interval between 2 DAM/IDAM measurements
acquisitions. Default value: 60minutes.
 Ri sample interval [hours]: The interval between 2 batteries internal resistance
measurements. Default value: 24hours.
BATTMASTER® user manual rev. 9
Page 21/49