System Design Issues and Challenges As a result, in order to properly ventilate the “critical” zone (Zone 3, in this example), the system must over-ventilate all other zones. Therefore, the air that returns from the “non-critical” zones (Zones 1 and 2) contains some “unused” or excess outdoor air. Most of this unused outdoor air recirculates back through the system, which allows the air-handling unit to bring in less than 40 percent outdoor air through the intake. But some of the unused outdoor air leaves the building in the exhaust air stream. In other words, some outdoor air enters the system, passes through non-critical zones, and then leaves the building without being fully used to dilute indoor contaminants. For this reason, multiple-zone recirculating systems have a system ventilation efficiency (Ev) that is less than 100 percent. Some of the outdoor air brought into the system is “wasted” because of over-ventilation in noncritical zones. However, as demonstrated below, multiple-zone recirculating systems can account for population diversity, which helps offset some of this inherent inefficiency. Calculating system intake airflow (Vot) For more information on ASHRAE Standard 62.1 and its procedures for calculating zone-level and system-level outdoor airflow requirements in a VAV system, refer to the Trane Engineers Newsletter Live broadcast DVD titled “ASHRAE Standard 62.1: Ventilation Requirements” (APP-CMC023-EN) or the following ASHRAE Journal articles: 1) Stanke, D. “Addendum 62n: SinglePath Multiple-Zone System Design.” ASHRAE Journal 47 (January 2005): 28– 35. Available at www.ashrae.org or www.trane.com. 2) Stanke, D. “Standard 62.1-2004: Designing Dual-Path, Multiple-Zone Systems.” ASHRAE Journal 47 (May 2005): 20–30. Available at www.ashrae.org or www.trane.com. ASHRAE Standard 62.1 defines a procedure to account for system ventilation efficiency, and to determine the system-level intake airflow (Vot)—the quantity brought through the outdoor-air damper in the air-handling unit— required to deliver the proper quantity of outdoor air to each of the individual zones. The standard provides two methods for determining system ventilation efficiency, Ev: • Table 6-3, “default Ev” method • Appendix A, “calculated Ev” method The default approach is simpler and takes less time than the calculated approach. However, the calculated approach is more accurate and usually results in higher efficiency and lower intake flow, and may be worth the added effort. Note: The examples below are not intended to reflect a real-life system, but rather to demonstrate the calculation methods, so the numbers used are simple rather than realistic. For more realistic examples, refer to the ASHRAE Journal articles listed in the sidebar. Table 6-3, “default Ev” method. Beginning with the default method, which uses Table 6-3 in the standard, determining system ventilation efficiency and the required outdoor-air intake flow involves several steps: 1 Calculate breathing-zone outdoor airflow (Vbz) 2 Determine the zone air-distribution effectiveness (Ez) 3 Calculate zone outdoor airflow (Voz) 4 Calculate the zone primary outdoor-air fraction (Zp) 5 Determine the “uncorrected” outdoor-air intake (Vou) SYS-APM008-EN Chilled-Water VAV Systems 105