Download Applications Engineering Manual - Chilled

Transcript
System Design Issues and Challenges
As a result, in order to properly ventilate the “critical” zone (Zone 3, in this
example), the system must over-ventilate all other zones. Therefore, the air
that returns from the “non-critical” zones (Zones 1 and 2) contains some
“unused” or excess outdoor air. Most of this unused outdoor air recirculates
back through the system, which allows the air-handling unit to bring in less
than 40 percent outdoor air through the intake. But some of the unused
outdoor air leaves the building in the exhaust air stream. In other words,
some outdoor air enters the system, passes through non-critical zones, and
then leaves the building without being fully used to dilute indoor
contaminants.
For this reason, multiple-zone recirculating systems have a system
ventilation efficiency (Ev) that is less than 100 percent. Some of the outdoor
air brought into the system is “wasted” because of over-ventilation in noncritical zones. However, as demonstrated below, multiple-zone recirculating
systems can account for population diversity, which helps offset some of this
inherent inefficiency.
Calculating system intake airflow (Vot)
For more information on ASHRAE
Standard 62.1 and its procedures for
calculating zone-level and system-level
outdoor airflow requirements in a VAV
system, refer to the Trane Engineers
Newsletter Live broadcast DVD titled
“ASHRAE Standard 62.1: Ventilation
Requirements” (APP-CMC023-EN) or the
following ASHRAE Journal articles:
1) Stanke, D. “Addendum 62n: SinglePath Multiple-Zone System Design.”
ASHRAE Journal 47 (January 2005): 28–
35. Available at www.ashrae.org or
www.trane.com.
2) Stanke, D. “Standard 62.1-2004:
Designing Dual-Path, Multiple-Zone
Systems.” ASHRAE Journal 47 (May
2005): 20–30. Available at
www.ashrae.org or www.trane.com.
ASHRAE Standard 62.1 defines a procedure to account for system ventilation
efficiency, and to determine the system-level intake airflow (Vot)—the
quantity brought through the outdoor-air damper in the air-handling unit—
required to deliver the proper quantity of outdoor air to each of the individual
zones.
The standard provides two methods for determining system ventilation
efficiency, Ev:
•
Table 6-3, “default Ev” method
•
Appendix A, “calculated Ev” method
The default approach is simpler and takes less time than the calculated
approach. However, the calculated approach is more accurate and usually
results in higher efficiency and lower intake flow, and may be worth the
added effort.
Note: The examples below are not intended to reflect a real-life system, but
rather to demonstrate the calculation methods, so the numbers used are
simple rather than realistic. For more realistic examples, refer to the ASHRAE
Journal articles listed in the sidebar.
Table 6-3, “default Ev” method. Beginning with the default method, which
uses Table 6-3 in the standard, determining system ventilation efficiency and
the required outdoor-air intake flow involves several steps:
1 Calculate breathing-zone outdoor airflow (Vbz)
2 Determine the zone air-distribution effectiveness (Ez)
3 Calculate zone outdoor airflow (Voz)
4 Calculate the zone primary outdoor-air fraction (Zp)
5 Determine the “uncorrected” outdoor-air intake (Vou)
SYS-APM008-EN
Chilled-Water VAV Systems
105