Download User`s Manual
Transcript
ACI MOD9200 MODBUS Gateway Programming Software d. Manually Resetting The Factory Default IP Address The Gateway can manually be reset to the default IP Address by moving the jumper (J6) from “Norm” to “Init”. Turn off the power to the Gateway and move the jumper from “Norm” to “Init”. Turn on power and the Gateway can be communicated with using the Factory Default IP Address 192.168.0.1 Subnet Mask 255.255.255.0. The Config File is no longer active while the jumper is in the “Init” position . A new Config File can be downloaded to the Gateway if desired. To reactivate the Config File - turn off the power to the Gateway and move the jumper back to “Norm”. Turn the power back on and the Config File will become active. The Gateway will have the IP Address that was set in the Config File. TCP/IP APPLICATION NOTE: When using the MOD9200D in TCP/IP mode the MODBUS Master “polling interval” should be set to occur within 2 minutes 59 seconds or less. If no polling activity occurs within 3 minutes the MOD9200D will automatically close the network connection and the MODBUS Master will have to close and re-open the connection to reestablish communications. The MODBUS Master should not attempt to reopen the network connection for at least 3 ½ minutes after the network connection has been closed. ---Only (1) TCP/IP connection is allowed at a time. P. 9 of 42 Automation Components Inc. 2305 Pleasant View Rd. Middleton, WI 53562 MOD Rev 8.0, 2011