MOD9200 MODBUS Gateway Programming Software
d. Manually Resetting The Factory Default IP Address

The Gateway can manually be reset to the default IP Address by
moving the jumper (J6) from “Norm” to “Init”.

Turn off the power to the Gateway and move the jumper from “Norm”
to “Init”. Turn on power and the Gateway can be communicated with
using the Factory Default IP Address 192.168.0.1 Subnet Mask
255.255.255.0. The Config File is no longer active while the jumper is
in the “Init” position . A new Config File can be downloaded to the
Gateway if desired.

To reactivate the Config File - turn off the power to the Gateway and
move the jumper back to “Norm”. Turn the power back on and the
Config File will become active. The Gateway will have the IP
Address that was set in the Config File.
TCP/IP APPLICATION NOTE: When using the MOD9200D in TCP/IP
mode the MODBUS Master “polling interval” should be set to occur within
2 minutes 59 seconds or less. If no polling activity occurs within 3 minutes
the MOD9200D will automatically close the network connection and the
MODBUS Master will have to close and re-open the connection to reestablish communications. The MODBUS Master should not attempt to reopen the network connection for at least 3 ½ minutes after the network
connection has been closed. ---Only (1) TCP/IP connection is allowed
at a time.