2.2 System Configuration Example for Micrex-SX programless communication
Point
●● Distributed placement of module-type temperature control system is possible by connecting several Ethernet communication
modules.
●● Control or Analog I/O module station number (“1” to “16”)
For proper communication, station number configuration is required. Set the leftmost module to “1” and set the rest of
modules to “2” to “16” consecutively starting from the left. Make sure not to duplicate station numbers in the system.
●● Event I/O module station number (“17” to “32”)
Event I/O module station number always starts from “17” and be set to the rest of unit consecutively form “18” to “32”. Make
sure not to duplicate station numbers in the system.
●● To use an Ethernet communication module, “connection permission of enhanced communication module (PUMC)”
parameter should be set to “1: PUMC connected (RS-485:disable)” with the PUM parameter loader.
Note
●● Do not install any broadcast communication devices such as a PC or a server on the Ethernet environment for PUMCE.
●● Use hubs and LAN cables for industrial use on the Ethernet environment for PUMCE.
●● Only one host device can access to PUMCE.
●● Connection between PUMCE and a host device is released if a preset amount of time has passed without communication.
Reconnect if the connection is dropped.
●● Be sure not to duplicate IP address.
Basic Setting Items
With this configuration, the following settings are required.
•• Ethernet communication setting
•• SX communication setting
•• SX device setting
•• Registration of setting area 1 to 712/ monitor area 1 to 712
2-6