WGW 3300 Basic 4.4.3.5 Alarm spread [ 7 ] Note! This function only takes effect in relay-mode (Stand-Alone operation) Is this value set to [ 1 ] „Spreading On“ then every teached in radio detector will be activated in case of a detected fire in the system. If the value is set to [ 0 ] then only the detector which has detected a fire will sound. 5 Operation mode „Loop“ The WGW 3300 Basic is a wireless-gateway of the series detect 3000. It can be integrated directly into the structure of a fire control panel “FCP”. The WGW 3300 Basic and every teached in detector within the WGW 3300 Basic will receive an unique address in the loop. 32-radio detectors can be operated at one WGW 3300 Basic. The amount of max.126 wired detectors in one loop decreases by the number of radio detectors programmed to the WGW 3300 Basic because every radio detector and the WGW will receive one of the possible 126 loop addresses on a wired loop. 5.1 Commissioning of the WGW 3300 Basic 5.1.1 Connecting the power supply Attention! Danger of an electric shock Turn the power off before working on electrical connections. The WGW 3300 Basic may only powered by 24V DC. You are not permitted to install a 230V-mains adapter into the WGW 3300 Basic box. Version 2.1 27