Transcript
MVI56-AFC ♦ ControlLogix Platform Liquid and Gas Flow Computer MVI56-AFC Sample Logic User Manual So you should select (check) the "Meter Configuration-> Ctrl Options->Treat Analysis as Process Input" check box: AFC56.Meters[ ].Analysis.Low_Precision Stores the analysis configuration to be used for the streams configured for low precision analysis. The sub-elements are defined as follows: Tag Description .Enable Set to 1 to update the stream analysis with the data at .Components. The user application must reset the value to interrupt the analysis update through the backplane. .Stream Select the stream number to be updated with the molar data .Components Contains the molar components in low precision (16-bit integer values) AFC56.Meters[ ].Analysis.High_Precision Stores the analysis configuration to be used for the streams configured for high precision analysis. The sub-elements are defined as follows: Note: Currently, this function is only available on the MVI56- AFC. For all other platforms continue to use AFC Manager 2.05 or earlier. Tag Description .Enable Set to 1 to update the stream analysis with the data at .Components. The sample logic will automatically reset the bit after requesting the update once. .Stream Select the stream number to be updated with the molar data .Components Contains the molar components in low precision (32-bit integer values) It is the user responsibility to update the correct tag (high or low precision) according to the stream configuration). The sample logic will not check if the update request will match the current stream configuration. ProSoft Technology, Inc. February 25, 2011 Page 233 of 316