Module Configuration User Manual 5.6 PTQ-104S Rev2 ♦ Quantum Platform IEC 60870-5-104 Server for Quantum [I104S] > [IEC-870-5-104] This section provides information required to configure a server application with the module. An item of concern is the maximum size of the total database. Although it is possible to configure a database of considerable size, the maximum Class 0 request may not exceed 2048 bytes in size. 5.6.1 Use IP List NO (0) or YES (1) This parameter specifies if the IP address of the host connected to the system will be validated. If the parameter is set to NO (0), any host may connect to the unit. If the parameter is set to YES (1), only hosts in the IP list will be permitted to connect to the unit. 5.6.2 Override StartDT NO (0) or YES (1) This parameter is used when testing the module with a simulator or with a Client unit that does not meet the IEC 60870-5-104 specification. After the Client connects to the module, it will send a STARTDT.ACT U-format message to the module to permit the module to start sending data. If the Client does not support this requirement, set the parameter to YES (1). Set the parameter to NO (0) if the Client sends the STARTDT.ACT message. Note: This parameter must be set to NO (0) if you wish to use the redundant Clients feature. Page 72 of 195 ProSoft Technology, Inc. March 4, 2013