Download TD 1000 PLUS

Transcript
TD 1000 PLUS
S E C O N D A R Y I N J E C T I O N R E L AY T E S T S E T
Frequency generator & frequency r.o.c.
Voltage measurement
. Possibility to change the frequency of the auxiliary AC
voltage output. Frequency generation characteristics:
. Frequency range: 15 Hz to 550 Hz.
. Frequency adjustment: 1 mHz.
. Rate of change: 1 mHz/s to 99.99 Hz/s.
OUTPUT
Auxiliary DC voltage output
. DC voltage range: 10...130 V or 20...240 V.
. DC voltage power: 90 W at full range, continuous duty,
with a current limit of 0.9 A @ 130 V and 0.45 A @ 240 V.
. Push-button to enable or disable the output
Timer
The electronic digital timer has a fully automatic start and stop,
both for make and break of the input, that can be either a clean
(dry) contact or a contact under voltage (wet).
. Metering range, can also be performed in cycles.
. Possibility to test automatic reclosers.
. Maximum number of reclosing commands: 99.
RANGE
From 0 to 9.999 s
From 10.0 to 99.99 s
From 100.0 to 999.9 s
From 1.000 to 9.999 s
RESOLUTION
ACCURACY
1 ms
10 ms
100 ms
1s
± (1 ms + 0.005%)
± (10 ms + 0.005%)
± (100 ms + 0.005%)
± (1 s + 0.005%)
RANGE
250 V AC
1.99V
19.99 V
199.9 V
299.9 V
300 V DC 19.99 V
199.9 V
399.9 V
65,130 V AC 19.99 V
199.9 V
260 V AC 19.99 V
199.9 V
299.9 V
20 A AC
20.00 A
130 V DC 19.99 V
199.9 V
260 V DC 19.99 V
199.9 V
299.9 V
RESOLUTION
1 mV
10 mV
100 mV
300 mV
10 mV
100 mV
300 mV
10 mV
100 mV
10 mV
100 mV
300 mV
10 mA
10 mV
100 mV
10 mV
100 mV
300 mV
. Via the multi-function menu knob it is possible to select the
measurement of angle or frequency.
. Readings, resolution and accuracy: see table.
Phase
Frequency
. Contacts range: 5 A; 250 V AC; 120 V DC.
± (1% + 50 mV)
± (1% + 50 mV)
± (1% + 200 mV)
± (1% + 300 mV)
± (0.5% + 50 mV)
± (0.5% + 200 mV)
± (0.5% + 300 mV)
± (1% + 20 mV)
± (1% + 200 mV)
± (1% + 20 mV)
± (1% + 200 mV)
± (1% + 300 mV)
± (1% + 30 mA)
± (0.5% + 20 mV)
± (0.5% + 200 mV)
± (0.5% + 20 mV)
± (0.5% + 200 mV)
± (0.5% + 300 mV)
Angle and frequency measurement
MEASUREMENT RANGE
2 auxiliary contacts are available
ACCURACY
0-360
15.000-499.999
RESOLUTION ACCURACY
1°
1 mHz
1° ± 1 Digit
±(0.1% + 1 mHz)
Other measurements
OUTPUT CURRENT AND VOLTAGE
MEASUREMENTS
. The following outputs are displayed at the same time on the LCD:
Current measurement
OUTPUT
10 A
40 A
100 A
RANGE
1.999 A
19.99 A
7.999 A
79.99 A
19.99 A
199.9 A
249.9 A
RESOLUTION
1
10
4
40
10
100
100
mA
mA
mA
mA
mA
mA
mA
ACCURACY
± (1% + 5 mA)
± (1% + 20 mA)
± (1% + 20 mA)
± (1% + 80 mA)
± (1% + 50 mA)
± (1% + 200 mA)
± (1% + 200 mA)
MEASUREMENT
Active Power, P = I*V*cos (j)
Reactive Power, Q = I*V*sin(j)
Apparent Power, S = I*V
Impedance, Z = V/I
Active Impedance Component, R = Z* cos(j)
Reactive Impedance Component, X = Z* sin(j)
UNIT
W
VAr
VA
Ohm, °
Ohm
Ohm
External inputs measurement
. It is possible to meter current or voltage input.
External current measurement
. Two inputs: 20 mA and 10 A.
3