TD 1000 PLUS S E C O N D A R Y I N J E C T I O N R E L AY T E S T S E T Frequency generator & frequency r.o.c. Voltage measurement . Possibility to change the frequency of the auxiliary AC voltage output. Frequency generation characteristics: . Frequency range: 15 Hz to 550 Hz. . Frequency adjustment: 1 mHz. . Rate of change: 1 mHz/s to 99.99 Hz/s. OUTPUT Auxiliary DC voltage output . DC voltage range: 10...130 V or 20...240 V. . DC voltage power: 90 W at full range, continuous duty, with a current limit of 0.9 A @ 130 V and 0.45 A @ 240 V. . Push-button to enable or disable the output Timer The electronic digital timer has a fully automatic start and stop, both for make and break of the input, that can be either a clean (dry) contact or a contact under voltage (wet). . Metering range, can also be performed in cycles. . Possibility to test automatic reclosers. . Maximum number of reclosing commands: 99. RANGE From 0 to 9.999 s From 10.0 to 99.99 s From 100.0 to 999.9 s From 1.000 to 9.999 s RESOLUTION ACCURACY 1 ms 10 ms 100 ms 1s ± (1 ms + 0.005%) ± (10 ms + 0.005%) ± (100 ms + 0.005%) ± (1 s + 0.005%) RANGE 250 V AC 1.99V 19.99 V 199.9 V 299.9 V 300 V DC 19.99 V 199.9 V 399.9 V 65,130 V AC 19.99 V 199.9 V 260 V AC 19.99 V 199.9 V 299.9 V 20 A AC 20.00 A 130 V DC 19.99 V 199.9 V 260 V DC 19.99 V 199.9 V 299.9 V RESOLUTION 1 mV 10 mV 100 mV 300 mV 10 mV 100 mV 300 mV 10 mV 100 mV 10 mV 100 mV 300 mV 10 mA 10 mV 100 mV 10 mV 100 mV 300 mV . Via the multi-function menu knob it is possible to select the measurement of angle or frequency. . Readings, resolution and accuracy: see table. Phase Frequency . Contacts range: 5 A; 250 V AC; 120 V DC. ± (1% + 50 mV) ± (1% + 50 mV) ± (1% + 200 mV) ± (1% + 300 mV) ± (0.5% + 50 mV) ± (0.5% + 200 mV) ± (0.5% + 300 mV) ± (1% + 20 mV) ± (1% + 200 mV) ± (1% + 20 mV) ± (1% + 200 mV) ± (1% + 300 mV) ± (1% + 30 mA) ± (0.5% + 20 mV) ± (0.5% + 200 mV) ± (0.5% + 20 mV) ± (0.5% + 200 mV) ± (0.5% + 300 mV) Angle and frequency measurement MEASUREMENT RANGE 2 auxiliary contacts are available ACCURACY 0-360 15.000-499.999 RESOLUTION ACCURACY 1° 1 mHz 1° ± 1 Digit ±(0.1% + 1 mHz) Other measurements OUTPUT CURRENT AND VOLTAGE MEASUREMENTS . The following outputs are displayed at the same time on the LCD: Current measurement OUTPUT 10 A 40 A 100 A RANGE 1.999 A 19.99 A 7.999 A 79.99 A 19.99 A 199.9 A 249.9 A RESOLUTION 1 10 4 40 10 100 100 mA mA mA mA mA mA mA ACCURACY ± (1% + 5 mA) ± (1% + 20 mA) ± (1% + 20 mA) ± (1% + 80 mA) ± (1% + 50 mA) ± (1% + 200 mA) ± (1% + 200 mA) MEASUREMENT Active Power, P = I*V*cos (j) Reactive Power, Q = I*V*sin(j) Apparent Power, S = I*V Impedance, Z = V/I Active Impedance Component, R = Z* cos(j) Reactive Impedance Component, X = Z* sin(j) UNIT W VAr VA Ohm, ° Ohm Ohm External inputs measurement . It is possible to meter current or voltage input. External current measurement . Two inputs: 20 mA and 10 A. 3