Maintenance
SCE/EN MF/C80
PACiS System Configuration Editor
2.5.5
Tap Changer
2.5.5.1
Position indicator
Page 51/112
Transformer
transformer
Tap changer
Tap pos ind
0
(A) Value features / minimum value
(A) Value features / maxmum value
0
S0276ENa
The following constraint between the two attributes must be respected:
("maximum value" − "minimum value" + 1) ∈ [1..64]
37087 / TapChanger / The result of Value features/maximum value - Value
features/minimum value + 1 is not in [2..64]
Moreover for analog TPI the following constraints must be respected:
•
current valid range (% maximum value) > (2 / (maximum acq. value - minimum acq.
value))
37212 / TapChanger / The constraint is not valid:[current valid range (% maximum value)
> (2 / (maximum acq. value - minimum acq. value))]
•
current valid range (% maximum value) < (100 / (maximum value - minimum value))
37212 / TapChanger / The constraint is not valid:[current valid range (% maximum value)
< (100 / (maximum value - minimum value))]
37363 Min and max value of transformer don't belong to the interval minimum value maximum value of the TPI (MinUsablePosition < MinScaledValue and/or MaxUsablePosition
> MaxScaledValue)
2.5.5.2
RaiseLower / GoToMinMax coherence
Transformer
transformer
Tap changer
Raise/lower DPC
Goto min/max DPC
(R) has for profile
DPC profile
(A) SBOMode
?
S0483ENa
On Tap changer, if the Raise/lower DPC is SBO Many, forbid the Goto min/max DPC
37178 / TapChanger / When Raise/lower DPC is SBO Many, Goto min/max DPC is not
allowed