SOLARDRIVE
PLUS
INSTALLATION AND
PROGRAMMING GUIDE
P013
Deceleration Time at Stop 2
Range
0 ÷ 32700
Default
Depending on size
Level
ADVANCED
Address
613
Function
Same as ramp 1 (see P010).
0 ÷ 327.00 s if P014=0 → 0.01 s
0 ÷ 3270.0 s if P014=1 → 0.1 s
0 ÷ 32700 s if P014=2 → 1 s
0 ÷ 327000 s if P014=3 → 10 s
NOTE
Values for ramp 2 can be applied to the reference provided that multiramp digital inputs are set up
and that ramp 2 is selected (for more details, contact Elettronica Santerno).
P014
Unit of Measure for Ramps 1 and 2
0 → 0.01 s
1 → 0.1 s
2→1s
3 → 10 s
Range
0÷3
Default
Depending on size
Level
ADVANCED
Address
614
Function
Defines the unit of measure for the time periods for speed ramp 1 (P009 and P010), for speed ramp 2
(P012 and P013), and for ramps in Fire Mode (P032 and P033). The allowable programmable range
may be extended from 0 s to 327000s.
E.g.
P014=1 then P009=100; this means P009 = 100 x 0.1 s = 10 s
P014=0 then P009=100; this means P009 = 100 x 0.01 s = 1 s
P014=3 then P009=100; this means P009 = 100 x 10 s = 1000 s
P015
Acceleration Time after Start
0 ÷ 327.00 s if P020=0 → 0.01 s
Range
0 ÷ 32700
Default
Depending on size
Level
ADVANCED
Address
615
Function
Ramp applied when the motor runs at constant speed and applied to the reference generated by the
algorithm for the Maximum Power Point Tracking (MPPT).
See also parameter P009 (ramp for motor stop).
103/160