Download SOLARDRIVE PLUS
Transcript
SOLARDRIVE PLUS INSTALLATION AND PROGRAMMING GUIDE M032 Range Active Address Function Instant Digital Inputs Bit-controlled measure See Table 18. Always active. 1682 Status of the virtual control terminal board before applying the timers to the digital inputs (if no timer is applied, it matches with M031). See Control Method Menu – section 6.6.6. Table 18: Coding of Measures M031, M032 Bit n. 0 1 2 3 4 M033 Range Active Address Function Digital Input MDI1 MDI2 MDI3(RESET) MDI4 MDI5 Bit n. 5 6 7 8 9 Digital Input MDI6/ECHA/FINA MDI7/ECHB MDI8/FINB ENABLE-SW ENABLE Local Control Terminal Board Bit-controlled measure See Table 19. Always active. 1683 Status of the digital inputs in the drive physical terminal board. The status of MDI2&S (S) input is the result of a logic AND between ENABLE-A and ENABLE-B physical signals. Table 19: Coding of Measures M033 Bit n. 0 1 2 3 6.5.4. Digital Input MDI1 MDI2&S (S) MDI3(RESET) MDI4 Bit n. 4 5 6 7 Digital Input MDI5 MDI6/ECHA/FINA MDI7/ECHB MDI8/FINB Outputs Menu This menu allows checking the status of the digital outputs, the analog outputs and the frequency outputs located in the terminal board. M056 Range Active Address Function Digital Outputs Bit-controlled measure See Table 20 Always active. 1706 Status of digital outputs MDO1÷4 and status of the precharge contactor. Table 20: Coding of Measure M056 Bit n°. 0 1 2 3 6 Digital Output MDO1/FOUT MDO2 MDO3 MDO4 Status of the precharge contactor 93/160