Download General Information
Transcript
Chapter 6 – Advanced Features elements / 4 intervals per hour). The Average Instantaneous Watt Delivered channel will report 1800. Table 1: Approximate Number of Days of Load Profile Storage (12-Channel Option) Interval Number of Load Profile Channels Used Length (minute 1 2 3 4 5 6 7 8 9 10 11 s) 1 49 24 16 12 9 8 7 6 5 4 4 2 98 49 32 24 19 16 14 12 10 9 8 3 147 73 49 36 29 24 21 18 16 14 13 4 196 98 65 49 39 32 28 24 21 19 17 5 245 122 81 61 49 40 35 30 27 24 22 6 294 147 98 73 58 49 42 36 32 29 26 10 490 245 163 122 98 81 70 61 54 49 44 12 588 294 196 147 117 98 84 73 65 58 53 15 736 368 245 184 147 122 105 92 81 73 66 20 981 490 327 245 196 163 140 122 109 98 89 147 736 490 368 294 245 210 184 163 147 133 30 2 294 147 981 736 588 490 420 368 327 294 267 60 4 2 12 4 8 12 16 20 24 40 49 61 81 122 245 Table 2: Approximate Number of Days of Load Profile Storage (4-Channel Standard) Interval Number of Load Profile Channels Used Length (minute 1 2 3 4 s) 1 17 8 5 4 2 34 17 11 8 3 51 25 17 12 4 68 34 22 17 5 85 42 28 21 6 102 51 34 25 10 170 85 56 42 12 204 102 68 51 15 256 128 85 64 20 341 170 113 85 30 512 256 170 128 102 60 512 341 256 4 JEMStar will record certain events in the Load Profile system intermixed with regular interval data. Any event that would end a Load Profile interval will be recorded, including the following: 101