Download VS mini J7 USER`S MANUAL
Transcript
Using Constant Copy Function Constant copy function The digital operator for remote operation (Model JVOP-146, Optional) can store constants for one inverter. A backup power supply is not necessary since EEPROM is used. Note: When using a digital operator for remote operation, use with a remote interface unit for remote operation (optional) and the cable for remote operation (optional). Refer to the VS mini J7 catalog (Literature No. KAE-S606-12) for details. Constant copy function is possible only for the inverters with same product series and power supply specifications. However, some constants may not be copied. It is also impossible to copy constants between VS mini and VS606V7 inverters. The prohibition of the reading of constants from the inverter can be set at n77. The constant data cannot be changed when this constant is set. If any alarm occurs during constant copy, the PRGM will blink and copying will continue. • Constant copy function selection (n76) Depending on the setting of n76 for constant copy function selection, the following functions are available: (1) Read all the constants from the inverter (READ) and store them in EEPROM in the digital operator. (2) Copies the constants stored in the digital operator to the inverter (COPY). (3) Verify that the constants in the digital operator and the constants in the inverter are the same (VERIFY). (4) Displays the maximum applicable motor capacity and the voltage class of the inverter that has the constants stored in the digital operator. (5) Displays the software number of the inverter that has the constants stored in the digital operator. 75