TECHNICAL DATA
& SERVICE MANUAL
GR9FI40R5IAA
OUTDOOR UNIT:
SPLIT SYSTEM AIR CONDITIONER
Model No.
Product Code No.
GR9FI40R5IAA
387107100
0.8180.598.01
09/2012
IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important to install or
service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in
this manual.
•The unit must be supplied with a dedicated electrical line.
• Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection
different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor,
or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.
WARNING
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.
When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and
then the wiring one; proceed in the reverse orden when removing
the units.
WARNING
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.
• Do not supply
power to the unit until all wiring and tubing are
0.8180.531.00
05/2007
completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
2
When servicing
• Turn the power OFF at the main power board before opening
the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no
metal scraps or bits of wiring have been left inside the unit being
serviced.
• Ventilate the room during the installation or testng the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.
Table of Contents
Page
1. OPERATING RANGE
4
2. SPECIFICATIONS
2-1 Unit Specifications
2-2 Major Component Specifications
2-3 Other Component Specifications
5
5
6
7
3. DIMENSIONAL DATA
8
4. REFRIGERANT FLOW DIAGRAM
9
5. PERFORMANCE DATA
5-1 Performance Charts
10
10
6. ELECTRICAL DATA
6-1 Electrical Characteristics
6-2 Electric Wiring Diagram
6-3 System Wiring Diagram
11
11
12
12
7. FUNCTION
7-1 Diagnostic
14
14
3
1. OPERATING RANGE
Cooling
Heating
Temperature
Maximum
Minimum
Maximum
Minimum
GR9FI40R5IAA
Indoor Air Intake Temp.
32°C D.B. / 23°C W.B.
10°C D.B. / 6°C W.B.
27°C D.B.
5°C D.B.
4
Outdoor Air Intake Temp.
43°C D.B.
-15°C D.B.
24°C D.B. / 18°C W.B.
-15°C D.B.
2. SPECIFICATIONS
2-1 Unit Specifications
GR9FI40R5IAA
Power source
220 - 240 V ~ 50 Hz
Voltage rating
230 V
Performance *
Capacity
MTA8FIA0R5I
kW
BTU/h
m³/h
Liters/h
Air circulation (High)
Moisture removal (High)
V
A
W
%
W/W
A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment
Refrigerant control
Power noise level
Hi
Refrigerant tubing connections
Max. allowable tubing length at shipment
Refrigerant
Narrow tube
tube diameter
Wide tube
Package dimensions
Weight
Heating
3,90
13307
600
1,5
-
Cooling
Electrical Rating
Available voltage range
Running amperes
Power input
Power factor
C.O.P.
Compressor locked rotor amperes
Dimensions & Weight
Unit dimensions
Cooling
3,50
11942
g
dB-A
m
mm(in.)
mm(in.)
Height
Width
Depth
Height
Width
Depth
Net
Shipping
mm
mm
mm
mm
mm
mm
kg
kg
m3
Shipping volume
Heating
198 ~ 264
4,40
950
94
3,68
-
4,30
930
94
4,19
-
Variable ( 200÷800 continuous )
Rotary (Hermetic) DC inverter
R410A / 1100
Electronic expansion valve
64
Flare type
15
6,35 (1/4)
9,52 (3/8)
630
830
345
710
990
410
40,0
45,0
0,29
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating Conditions are:
Cooling: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B. / 24°C W.B.
Heating: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
5
2-2 Major Component Specifications
GR9FI40R5IAA
Compressor
Type
Compressor model
Nominal input (compressor rating condition)
Compressor oil…Amount
Coil resistance (Ambient temp. 20°C)
Overload relay
Safety devices
Type
Operating Temp. Open
Close
Fan & Fan Motor
Type
Q'ty ……. Ø
Fan motor model…Q'ty
No. Of poles…rpm
Nominal output
Coil resistance (Ambient temp. 25 °C )
Safety devices
W
cc
Ω
°C
°C
°C
°C
Propeller
1…. Ø 400
P35810 P0012
8 ... variable ( 200 ÷ 800 )
20
BRN-BLK: 210
YEL-BLK: 210
BRN-YEL: 210
-
mm
m2
Aluminium plate fin / Copper tube
2
1,5
0,47
Nr. … mm
W
Ω
Type
Operating temp. Open
Close
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
Rotary (Hermetic) DC inverter
5RS102XBE01
985
RB68A …… 320
0,858
Software Protection
-
Acrylic baked-on enamel finish
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6
2-3 Other Component Specifications
GR9FI40R5IAA
4-way Valve (20S)
Coil rating
Coil resistance
Electronic Expansion Valve
Coil rating
Coil resistance / phase
Defrost Valve
Coil rating
Coil resistance
Ω (at 20°C)
SQ-136 (Coil) SHF-4H-23U (Valve)
AC 220/240 V, 50 Hz
1440 ± 5%
Ω (at 20°C)
ZCAM-MD12EX(Coil) ZCAM-BD15EX (Valve)
DC 12 V
46 ± 4%
Ω (at 20°C)
FQ-235-RK (Coil) FDF6A-049-RK (Valve)
AC 220/240 V - 50 Hz
1273 ± 10%
Thermistor (coil sensor)
Resistance
kΩ
NTC-THERMISTOR
10 at 25 °C
Thermistor (compressor discharge sensor)
Resistance
kΩ
NTC-THERMISTOR
10 at 25 °C
Thermistor (inlet air sensor)
Resistance
kΩ
NTC-THERMISTOR
10 at 25 °C
Crank case heater
Resistance
Base heater
Resistance
Ω (at 20°C)
30 W RESISTANCE
1760 ± 10%
Ω (at 20°C)
SILICON RESISTANCE 75W
705 ± 10%
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7
3. DIMENSIONAL DATA
GR9FI40R5IAA
4 - Ø12
for anchor bolt
WIDE TUBE ø.9,52 (3/8")
NARROW TUBE ø.6,35 (1/4")
dimension [mm]
8
4. REFRIGERANT FLOW DIAGRAM
Outdoor Unit:
Indoor Unit:
GR9FI40R5IAA
MTA8FIA0R5I
MTA8FBIA0R5I CA8FIA0R5I KPA8FIA0R5I SDA8FIA0R5I
Outdoor Unit
Indoor Unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this
air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation,
both tubes must be well insulated with a proper insulation material.
The thickness of the insulation should be a min. 8mm.
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve
because it can cause the tube to break or crack.
9
5. PERFORMANCE DATA
5-1 Performance charts
GR9FI40R5IAA
Cooling Characteristics
Heating Characteristics
6,0
5,5
Indoor inlet air
D.B. (°C)
Indoor inlet air
D.B. (°C)
5,0
5,5
32
25
Operating current (A)
Operating current (A)
4,5
4,0
27
3,5
19
5,0
20
4,5
32
15
4,0
27
3,0
19
2,5
3,5
1
2,0
10
15
20
25
30
35
3,0
40
0
Outdoor inlet air D.B. temperature (°C)
5
7
10
15
20
Outdoor inlet D.B. temperature (°C)
3,60
1,10
Indoor inlet air
D.B. (°C)
3,40
Indoor inlet air
D.B. (°C)
High pressure at wide tube service valve Mpa
Low pressure at wide tube service valve MPa
1,00
0,90
32
0,80
27
0,70
19
0,60
0.8180.531.00
05/2007
0,50
3,20
25
3,00
20
2,80
15
2,60
2,40
2,20
2,00
10
15
20
25
30
35
40
0
Outdoor inlet air D.B. temperature (°C)
5
7
10
15
20
Outdoor inlet air D.B. temperature (°C)
Note
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches
extremely high values in heating mode.
Points of Rating condition
Data referred to
10
MTA8FIA0R5I
6. ELECTRICAL DATA
6-1 Electrical characteristics
OUTDOOR UNIT:
GR9FI40R5IAA
COOLING
Indoor Unit
Fan Motor
Performance at
Rating conditions
Rating Conditions:
Running Amps.
Power input
A
kW
0,13
0,031
Outdoor unit
Fan Motor + Compressor
230 V - 1 Phase - 50 Hz
4,27
0,919
Complete Unit
4,4
0,950
Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B. / 24°C W.B.
HEATING
Indoor Unit
Fan Motor
Performance at
Rating conditions
Rating Conditions:
Running Amps.
Power input
A
kW
0,13
0,031
Outdoor unit
Fan Motor + Compressor
230 V - 1 Phase - 50 Hz
4,17
0,899
Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
NOTE: Data referred to indoor unit
MTA8FIA0R5I
model.
For other indoor unit models there could be some differences.
11
Complete Unit
4,3
0,930
6-2 Electric Wiring Diagram
6-3 System Wiring Diagram
Wiring diagram for all units except hi-wall
12
Wiring diagram for all units
Wiring diagram for all unit except hi-wall
13
7. FUNCTION
7-1 Diagnostic
With this feature is possible to have a visual signal that a trouble is occurring.
This mode is always active and the signalling is made through the display board LEDS .
In case of no troubles the LEDS status follows its normal function.
The detected troubles are showed to the user/technician using the 3 or 5 leds of the indoor unit receiver
and the 5 leds on the outdoor pcb. For each fault there are different effects upon the operation of the A/C:
NOTES
The troubles are showed according to a priority list that is in case of more than one trouble present,
is always showed, at first, the one with the highest priority (3 2 1 etc).
Sensor damaged means a situation where sensor is short-circuited or opened.
In case of damaged sensors, the system (CM, FMO, FMI etc), if in OFF state, does not start.
EFFECTS
system does not operate
as soon as fault is cleared,
the system automatically
re-start after 3 min.
during this time,
the signalling is showed
14
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728