Download technical data & service manual split system air conditioner
Transcript
TECHNICAL DATA & SERVICE MANUAL GR9FI40R5IAA OUTDOOR UNIT: SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GR9FI40R5IAA 387107100 0.8180.598.01 09/2012 IMPORTANT! Please read before installation This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently. For safe installation and trouble-free operation, you must: • Carefully read this instruction booklet before beginning. • Follow each installation or repair step exactly as shown. • Observe all local, state and national electrical codes. • Pay close attention to all warning and caution notices given in this manual. •The unit must be supplied with a dedicated electrical line. • Ground the unit following local electrical codes. • The Yellow/Green wire cannot be used for any connection different from the ground connection. • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. • Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. • Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line. When transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers. WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If necessary, get help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions. In case of improper installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. When installing... ... In a ceiling or wall Make sure the ceiling/wall is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support. ... In a room Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors. ... In moist or uneven locations Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations. ... In area with strong winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle. ... In a snowy area (for heat pump-type systems) Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents. SPECIAL PRECAUTIONS • During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units. WARNING When wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM. When connecting refrigerant tubing • Keep all tubing runs as short as possible. • Use the flare method for connecting tubing. • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection. • Check carefully for leaks before starting the test run. NOTE: Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas. • Do not supply power to the unit until all wiring and tubing are 0.8180.531.00 05/2007 completed or reconnected and checked, to ensure the grounding. • Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death. 2 When servicing • Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. • Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources. Table of Contents Page 1. OPERATING RANGE 4 2. SPECIFICATIONS 2-1 Unit Specifications 2-2 Major Component Specifications 2-3 Other Component Specifications 5 5 6 7 3. DIMENSIONAL DATA 8 4. REFRIGERANT FLOW DIAGRAM 9 5. PERFORMANCE DATA 5-1 Performance Charts 10 10 6. ELECTRICAL DATA 6-1 Electrical Characteristics 6-2 Electric Wiring Diagram 6-3 System Wiring Diagram 11 11 12 12 7. FUNCTION 7-1 Diagnostic 14 14 3 1. OPERATING RANGE Cooling Heating Temperature Maximum Minimum Maximum Minimum GR9FI40R5IAA Indoor Air Intake Temp. 32°C D.B. / 23°C W.B. 10°C D.B. / 6°C W.B. 27°C D.B. 5°C D.B. 4 Outdoor Air Intake Temp. 43°C D.B. -15°C D.B. 24°C D.B. / 18°C W.B. -15°C D.B. 2. SPECIFICATIONS 2-1 Unit Specifications GR9FI40R5IAA Power source 220 - 240 V ~ 50 Hz Voltage rating 230 V Performance * Capacity MTA8FIA0R5I kW BTU/h m³/h Liters/h Air circulation (High) Moisture removal (High) V A W % W/W A Features Fan speed Compressor Refrigerant / Amount charged at shipment Refrigerant control Power noise level Hi Refrigerant tubing connections Max. allowable tubing length at shipment Refrigerant Narrow tube tube diameter Wide tube Package dimensions Weight Heating 3,90 13307 600 1,5 - Cooling Electrical Rating Available voltage range Running amperes Power input Power factor C.O.P. Compressor locked rotor amperes Dimensions & Weight Unit dimensions Cooling 3,50 11942 g dB-A m mm(in.) mm(in.) Height Width Depth Height Width Depth Net Shipping mm mm mm mm mm mm kg kg m3 Shipping volume Heating 198 ~ 264 4,40 950 94 3,68 - 4,30 930 94 4,19 - Variable ( 200÷800 continuous ) Rotary (Hermetic) DC inverter R410A / 1100 Electronic expansion valve 64 Flare type 15 6,35 (1/4) 9,52 (3/8) 630 830 345 710 990 410 40,0 45,0 0,29 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks: Rating Conditions are: Cooling: Indoor Air Temperature 27°C D.B. / 19°C W.B. Outdoor Air Temperature 35°C D.B. / 24°C W.B. Heating: Indoor Air Temperature 20°C D.B. Outdoor Air Temperature 7°C D.B. / 6°C W.B. * For other INDOOR UNITS' MODELS, please refer to catalogue 5 2-2 Major Component Specifications GR9FI40R5IAA Compressor Type Compressor model Nominal input (compressor rating condition) Compressor oil…Amount Coil resistance (Ambient temp. 20°C) Overload relay Safety devices Type Operating Temp. Open Close Fan & Fan Motor Type Q'ty ……. Ø Fan motor model…Q'ty No. Of poles…rpm Nominal output Coil resistance (Ambient temp. 25 °C ) Safety devices W cc Ω °C °C °C °C Propeller 1…. Ø 400 P35810 P0012 8 ... variable ( 200 ÷ 800 ) 20 BRN-BLK: 210 YEL-BLK: 210 BRN-YEL: 210 - mm m2 Aluminium plate fin / Copper tube 2 1,5 0,47 Nr. … mm W Ω Type Operating temp. Open Close Heat Exch. Coil Coil Rows Fin pitch Face area Rotary (Hermetic) DC inverter 5RS102XBE01 985 RB68A …… 320 0,858 Software Protection - Acrylic baked-on enamel finish External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 6 2-3 Other Component Specifications GR9FI40R5IAA 4-way Valve (20S) Coil rating Coil resistance Electronic Expansion Valve Coil rating Coil resistance / phase Defrost Valve Coil rating Coil resistance Ω (at 20°C) SQ-136 (Coil) SHF-4H-23U (Valve) AC 220/240 V, 50 Hz 1440 ± 5% Ω (at 20°C) ZCAM-MD12EX(Coil) ZCAM-BD15EX (Valve) DC 12 V 46 ± 4% Ω (at 20°C) FQ-235-RK (Coil) FDF6A-049-RK (Valve) AC 220/240 V - 50 Hz 1273 ± 10% Thermistor (coil sensor) Resistance kΩ NTC-THERMISTOR 10 at 25 °C Thermistor (compressor discharge sensor) Resistance kΩ NTC-THERMISTOR 10 at 25 °C Thermistor (inlet air sensor) Resistance kΩ NTC-THERMISTOR 10 at 25 °C Crank case heater Resistance Base heater Resistance Ω (at 20°C) 30 W RESISTANCE 1760 ± 10% Ω (at 20°C) SILICON RESISTANCE 75W 705 ± 10% DATA SUBJECT TO CHANGE WITHOUT NOTICE 7 3. DIMENSIONAL DATA GR9FI40R5IAA 4 - Ø12 for anchor bolt WIDE TUBE ø.9,52 (3/8") NARROW TUBE ø.6,35 (1/4") dimension [mm] 8 4. REFRIGERANT FLOW DIAGRAM Outdoor Unit: Indoor Unit: GR9FI40R5IAA MTA8FIA0R5I MTA8FBIA0R5I CA8FIA0R5I KPA8FIA0R5I SDA8FIA0R5I Outdoor Unit Indoor Unit Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8mm. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. 9 5. PERFORMANCE DATA 5-1 Performance charts GR9FI40R5IAA Cooling Characteristics Heating Characteristics 6,0 5,5 Indoor inlet air D.B. (°C) Indoor inlet air D.B. (°C) 5,0 5,5 32 25 Operating current (A) Operating current (A) 4,5 4,0 27 3,5 19 5,0 20 4,5 32 15 4,0 27 3,0 19 2,5 3,5 1 2,0 10 15 20 25 30 35 3,0 40 0 Outdoor inlet air D.B. temperature (°C) 5 7 10 15 20 Outdoor inlet D.B. temperature (°C) 3,60 1,10 Indoor inlet air D.B. (°C) 3,40 Indoor inlet air D.B. (°C) High pressure at wide tube service valve Mpa Low pressure at wide tube service valve MPa 1,00 0,90 32 0,80 27 0,70 19 0,60 0.8180.531.00 05/2007 0,50 3,20 25 3,00 20 2,80 15 2,60 2,40 2,20 2,00 10 15 20 25 30 35 40 0 Outdoor inlet air D.B. temperature (°C) 5 7 10 15 20 Outdoor inlet air D.B. temperature (°C) Note Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode. Points of Rating condition Data referred to 10 MTA8FIA0R5I 6. ELECTRICAL DATA 6-1 Electrical characteristics OUTDOOR UNIT: GR9FI40R5IAA COOLING Indoor Unit Fan Motor Performance at Rating conditions Rating Conditions: Running Amps. Power input A kW 0,13 0,031 Outdoor unit Fan Motor + Compressor 230 V - 1 Phase - 50 Hz 4,27 0,919 Complete Unit 4,4 0,950 Indoor Air Temperature 27°C D.B. / 19°C W.B. Outdoor Air Temperature 35°C D.B. / 24°C W.B. HEATING Indoor Unit Fan Motor Performance at Rating conditions Rating Conditions: Running Amps. Power input A kW 0,13 0,031 Outdoor unit Fan Motor + Compressor 230 V - 1 Phase - 50 Hz 4,17 0,899 Indoor Air Temperature 20°C D.B. Outdoor Air Temperature 7°C D.B. / 6°C W.B. NOTE: Data referred to indoor unit MTA8FIA0R5I model. For other indoor unit models there could be some differences. 11 Complete Unit 4,3 0,930 6-2 Electric Wiring Diagram 6-3 System Wiring Diagram Wiring diagram for all units except hi-wall 12 Wiring diagram for all units Wiring diagram for all unit except hi-wall 13 7. FUNCTION 7-1 Diagnostic With this feature is possible to have a visual signal that a trouble is occurring. This mode is always active and the signalling is made through the display board LEDS . In case of no troubles the LEDS status follows its normal function. The detected troubles are showed to the user/technician using the 3 or 5 leds of the indoor unit receiver and the 5 leds on the outdoor pcb. For each fault there are different effects upon the operation of the A/C: NOTES The troubles are showed according to a priority list that is in case of more than one trouble present, is always showed, at first, the one with the highest priority (3 2 1 etc). Sensor damaged means a situation where sensor is short-circuited or opened. In case of damaged sensors, the system (CM, FMO, FMI etc), if in OFF state, does not start. EFFECTS system does not operate as soon as fault is cleared, the system automatically re-start after 3 min. during this time, the signalling is showed 14 R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France Tél. 04.74.00.92.92 - Fax 04.74.00.42.00 R.C.S. Bourg-en-Bresse B 759 200 728