Download Urban Multi

Transcript
Troubleshooting
3.7
PACD011001C2
Indoor Unit: Drain Level above Limit
Remote Controller
Display
Supposed Causes
AF
„ Humidifier unit (optional accessory) leaking
„ Defect of drain pipe (upward slope, etc.)
„ Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Field drain
piping has a defect such as
upward sloping.
YES
Modify the drain piping.
NO
A humidifier
unit (optional accessory) is
installed on the indoor
unit.
NO
YES
Check if the humidifier unit is leaking.
Defect of indoor unit PC board
(VF034)
350