Troubleshooting 3.7 PACD011001C2 Indoor Unit: Drain Level above Limit Remote Controller Display Supposed Causes AF „ Humidifier unit (optional accessory) leaking „ Defect of drain pipe (upward slope, etc.) „ Defect of indoor unit PC board Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred. Field drain piping has a defect such as upward sloping. YES Modify the drain piping. NO A humidifier unit (optional accessory) is installed on the indoor unit. NO YES Check if the humidifier unit is leaking. Defect of indoor unit PC board (VF034) 350 Troubleshooting Urban Multi “MX1R, ME1R Series” Using R-407C