PACD011001C2
Operation Flowcharts
Cooling operation
∗18
Start control in progress?
YES
NO
YES
Oil equalization in progress?
NO
∗19
Compressor
protection operation
in progress?
YES
NO
∗22
Low temperature
protection operation in
progress?
YES
NO
Inverter compressor magnetic
K1M
contactor
Inverter output frequency
INV
Standard compressor
K2M
magnetic contactor
Y1E
Electronic expansion
valve
Solenoid valve (hot gas)
ON
30~116 Hz by PI
control ∗20
ON/OFF by PI
control
OFF
38 Hz
42 Hz
ON
OFF
Open
OFF
Y2S
Solenoid valve (injection) Y3S
Y4S
∗21
Y1R
4-way valve
M1F
Fan
M2F
Fan
30~116 Hz by PI and
protective control
ON/OFF by PI and
protective control
30~116 Hz
ON/OFF by
saturation
temperature
corresponding to
suction pressure
OFF
ON
ON/OFF by discharge temperature protection control
ON
OFF
H
ON
H
ON
∗22
B
Troubleshooting Urban Multi “MX1, ME1 Series” Using R-22
(VF027)