Download TECHNICAL & SERVICE MANUAL
Transcript
• Name, Symbol and the Maximum Remote controller Units for Connection Name Outdoor unit Indoor unit Symbol OC IC M-NET remote controller RC Maximum units for connection — 1 OC unit can be connected to 1~9 (P112)/1~10 (P125)/1~12 (P140) IC units Maximum 2 RC for 1 indoor unit, Maximum 12 RC for 1 OC Permissible Lengths Longest transmission cable length (1.25 mm²) L1 + L2, L2 + L3, L3 + L1 [ 200m Remote controller cable length 1. If 0.5 to 1.25 mm² R1, R2 [10m 2. If the length exceeds 10 meters, the exceeding section should be 1.25 mm² and that section should be a value within the total extension length of the transmission cable and maximum transmission cable length. (L3) Prohibited items • M-NET remote controller (RC) and MA remote controller (MA) cannot be used together. • Do not connect anything with TB15 of indoor unit (IC). OC 51 IC IC 01 02 TB3 TB7 TB5 TB15 TB5 TB15 M1 M2 S M1 M2 S M1 M2 S 1 2 M1 M2 S 1 2 A B A B TB15 101 MA RC Same as above OC 51 TB3 M1 M2 S Same as above IC IC 01 02 TB7 TB5 TB15 TB5 TB15 M1 M2 S M1 M2 S 1 2 M1 M2 S 1 2 A B A B A B A B A B 101 151 102 103 104 RC (Main) RC (Sub) RC (Main) RC (Sub) RC OC 51 IC(Main) IC(Sub) 01 02 TB3 TB7 TB5 TB15 TB5 TB15 M1 M2 S M1 M2 S M1 M2 S 1 2 M1 M2 S 1 2 A B 102 RC OCH547 • Use the indoor unit (IC) address plus 150 as the sub remote controller address. In this case, it should be 152. • 3 or more remote controller (RC) cannot be connected to 1 indoor unit. 27 • The remote controller address is the indoor unit main address plus 100. In this case, it should be 101.