Download POWER NETWORK PARAMETER METER
Transcript
9. TECHNICAL DATA Measuring ranges and admissible basic errors are presented in the table 8 Table 8 Measured quantity Range Basic error Remarks U i voltage 57.7/100 V (Ku=1) 230/400 V (Ku=1) 400/ 690 V (Ku =1) dla Ku1...1,6 MV (0.2% m.v.+0.1% range) Ku = 1...4000 (max 1.6 MV) I i current 1.000 A (Ki=1) 5.000 A (Ki=1) dla Ki1...45 kA (0.2% m.v.+0.1% range) Ki = 1...9000 (max 45 kA) P i active power PAV mean active power Active energy EnP S i apparent power Apparent energy EnS Q i reactive power Reactive energy EnQ 0.0... 999.9 W for Ku1, Ki1 (-)220 GW (0.5% m.v.+0.2% range) 0.0...999.9 VA for Ku1, Ki1 220 GVA (0.5% m.v.+0.2% range) 0.0... 999.9 Var for Ku1, Ki1 (-)220 GVar (0.5% m.v.+0.2% range) - 1.00 ...0.00 ...1.000 1% m.v. 2c Pf=Power factor=P/S t i factor (ratio of reactive power to active power) - 99.9....0....99.9 1% m.v. 2c error in the range - 99.9...0...99.9 f frequency 20.0... 500.0 Hz 0.5% m.v. 0.5...100% 5% m.v. 2c Pf i active power factor THD Ui, THD Ii Where: Ku - voltage transformer ratio Ki - current transformer ratio m.v. - measured value c - less significant display digit 28 -10%Un <Un < 12%Un In > 10% In 47... 52 Hz