Download Compact link module (EH-TLNKE) APPLICATION
Transcript
Chapter 7 Daily and Periodic Inspection 7.1 Daily inspection Verify the following items while the system is running. Please refer to Chapter 3 for detail of LED display, and Chapter 6 for detail of error indication and countermeasure. Table 7.1.1 Items for daily inspection of link module Item Inspection method LED Normal status Abnormal status Confirmation of operation Watching POW LED RUN LED Lighting Off Confirmation of error Watching HERR LED CERR LED Off Lighting /blinking Confirmation of communication data Watching TxD LED RxD LED Blinking /lighting thinly 7.2 Always lightning or off Main cause of error • Power LED off: 5V DC power malfunction • RUN LED off: communication is stopped • HERR LED lightning: breakdown of module • CERR LED lightning: time-out error • TxD LED off: breakdown of link module etc. • RxD LED off: disconnection of line etc. Periodic inspection Turn off the power for the external I/O circuits and link system, check the following items. Table 7.1.2 Items for periodic inspection of link module Item Method All screws of connecter for communication are tight. Tighten surly. Removal of dust on case and connecter. Removal with cleaner etc. Periodic inspection must be done once every 6 months at least. Please bring the check cycle forward with respondent to the installation environments such as the vibration and dust. 7–1