Download caution! - Climatemaster
Transcript
THE SMART SOLUTION FOR ENERGY EFFICIENCY Tr a n q u i l i t y ® ( T R ) S e r i e s R e v. : 0 7 / 1 8 / 1 3 Electrical - Line Voltage Table 4a: Tranquility® TR Series Electrical Data - (Standard 60Hz Units) TR Model 006 009 012 015 018 024 030 036 042 048 060 QTY RLA LRA Fan Motor FLA 197/254 1 3.3 17.7 0.40 3.7 4.5 239/292 1 2.9 13.5 0.40 3.3 4.0 15 208-230/60/1 197/254 1 4.5 22.2 0.92 5.4 6.5 15 E 265/60/1 239/292 1 3.8 18.8 0.70 4.5 5.5 15 G 208-230/60/1 197/254 1 5.1 32.5 0.92 6.0 7.3 15 E 265/60/1 239/292 1 4.0 31.5 0.70 4.7 5.7 15 G 208-230/60/1 197/254 1 6.0 29.0 1.20 7.2 8.7 15 E 265/60/1 239/292 1 5.4 28.0 0.86 6.8 8.2 15 G 208-230/60/1 197/254 1 7.2 33.0 1.20 8.4 10.2 15 E 265/60/1 239/292 1 5.9 28.0 0.86 6.8 8.2 15 G 208-230/60/1 197/254 1 12.8 58.3 1.50 14.3 17.5 30 E 265/60/1 239/292 1 9.6 54.0 1.30 10.9 13.3 20 H 208-230/60/3 197/254 1 7.7 55.4 1.50 9.2 11.1 15 F 460/60/3 414/506 1 3.6 28.0 0.76 4.4 5.3 15 G 208-230/60/1 197/254 1 14.1 73.0 3.00 17.1 20.6 30 E 265/60/1 239/292 1 11.2 60.0 2.70 13.9 16.7 25 H 208-230/60/3 197/254 1 8.9 58.0 3.00 11.9 14.1 20 F 460/60/3 414/506 1 4.2 28.0 1.70 5.9 7.0 15 G 208-230/60/1 197/254 1 16.7 79.0 1.80 18.5 22.7 35 E 265/60/1 239/292 1 13.5 72.0 2.00 15.5 18.9 30 H 208-230/60/3 197/254 1 10.4 73.0 1.80 12.2 14.8 25 F 460/60/3 414/506 1 5.8 38.0 1.24 7.0 8.5 15 G 208-230/60/1 197/254 1 17.9 112.0 3.00 20.9 25.4 40 H 208-230/60/3 197/254 1 13.5 88.0 3.00 16.5 19.9 30 Voltage Code Rated Voltage Voltage Min/Max G 208-230/60/1 E 265/60/1 G Compressor Total Unit FLA Min Circuit Amp Max Fuse/ HACR 15 F 460/60/3 414/506 1 6.0 44.0 1.70 7.7 9.2 15 N 575/60/3 518/633 1 4.9 34.0 1.40 6.3 7.5 15 G 208-230/60/1 197/254 1 21.8 117.0 3.40 25.2 30.7 50 H 208-230/60/3 197/254 1 13.7 83.1 3.40 17.1 20.5 30 F 460/60/3 414/506 1 6.2 41.0 1.80 8.0 9.6 15 N 575/60/3 518/633 1 4.8 33.0 1.40 6.2 7.4 15 G 208-230/60/1 197/254 1 26.3 134.0 4.90 31.2 37.8 60 H 208-230/60/3 197/254 1 15.6 110.0 4.90 20.5 24.4 40 F 460/60/3 414/506 1 7.8 52.0 2.50 10.3 12.3 20 N 575/60/3 518/633 1 5.8 38.9 1.90 7.7 9.2 15 HACR circuit breaker in USA only All fuses Class RK-5 c l i m a t e m a s t e r. c o m 21