THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tr a n q u i l i t y ® ( T R ) S e r i e s
R e v. : 0 7 / 1 8 / 1 3
Electrical - Line Voltage
Table 4a: Tranquility® TR Series Electrical Data - (Standard 60Hz Units)
TR
Model
006
009
012
015
018
024
030
036
042
048
060
QTY
RLA
LRA
Fan
Motor
FLA
197/254
1
3.3
17.7
0.40
3.7
4.5
239/292
1
2.9
13.5
0.40
3.3
4.0
15
208-230/60/1
197/254
1
4.5
22.2
0.92
5.4
6.5
15
E
265/60/1
239/292
1
3.8
18.8
0.70
4.5
5.5
15
G
208-230/60/1
197/254
1
5.1
32.5
0.92
6.0
7.3
15
E
265/60/1
239/292
1
4.0
31.5
0.70
4.7
5.7
15
G
208-230/60/1
197/254
1
6.0
29.0
1.20
7.2
8.7
15
E
265/60/1
239/292
1
5.4
28.0
0.86
6.8
8.2
15
G
208-230/60/1
197/254
1
7.2
33.0
1.20
8.4
10.2
15
E
265/60/1
239/292
1
5.9
28.0
0.86
6.8
8.2
15
G
208-230/60/1
197/254
1
12.8
58.3
1.50
14.3
17.5
30
E
265/60/1
239/292
1
9.6
54.0
1.30
10.9
13.3
20
H
208-230/60/3
197/254
1
7.7
55.4
1.50
9.2
11.1
15
F
460/60/3
414/506
1
3.6
28.0
0.76
4.4
5.3
15
G
208-230/60/1
197/254
1
14.1
73.0
3.00
17.1
20.6
30
E
265/60/1
239/292
1
11.2
60.0
2.70
13.9
16.7
25
H
208-230/60/3
197/254
1
8.9
58.0
3.00
11.9
14.1
20
F
460/60/3
414/506
1
4.2
28.0
1.70
5.9
7.0
15
G
208-230/60/1
197/254
1
16.7
79.0
1.80
18.5
22.7
35
E
265/60/1
239/292
1
13.5
72.0
2.00
15.5
18.9
30
H
208-230/60/3
197/254
1
10.4
73.0
1.80
12.2
14.8
25
F
460/60/3
414/506
1
5.8
38.0
1.24
7.0
8.5
15
G
208-230/60/1
197/254
1
17.9
112.0
3.00
20.9
25.4
40
H
208-230/60/3
197/254
1
13.5
88.0
3.00
16.5
19.9
30
Voltage
Code
Rated
Voltage
Voltage
Min/Max
G
208-230/60/1
E
265/60/1
G
Compressor
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
15
F
460/60/3
414/506
1
6.0
44.0
1.70
7.7
9.2
15
N
575/60/3
518/633
1
4.9
34.0
1.40
6.3
7.5
15
G
208-230/60/1
197/254
1
21.8
117.0
3.40
25.2
30.7
50
H
208-230/60/3
197/254
1
13.7
83.1
3.40
17.1
20.5
30
F
460/60/3
414/506
1
6.2
41.0
1.80
8.0
9.6
15
N
575/60/3
518/633
1
4.8
33.0
1.40
6.2
7.4
15
G
208-230/60/1
197/254
1
26.3
134.0
4.90
31.2
37.8
60
H
208-230/60/3
197/254
1
15.6
110.0
4.90
20.5
24.4
40
F
460/60/3
414/506
1
7.8
52.0
2.50
10.3
12.3
20
N
575/60/3
518/633
1
5.8
38.9
1.90
7.7
9.2
15
HACR circuit breaker in USA only
All fuses Class RK-5
c l i m a t e m a s t e r. c o m