Download Models 8681/8681_BAC SureFlow Adaptive Offset Controller
Transcript
40 SUPPLY FLOW MENU (continued) MENU ITEM SUPPLY FLOW LOW CALIBRATION SOFTWARE NAME SUP LOW CAL ITEM DESCRIPTION The SUP LOW CAL menu items display the currently measured supply flow rate and the calibrated value for that supply flow. The supply dampers move to the SUP LOW SETP damper position for the low calibration. The calibrated supply flow can be adjusted using the / keys to make it match a reference measurement. Pressing the SELECT key saves the new calibration data. ITEM RANGE DEFAULT VALUE SUPPLY FLOW HIGH CALIBRATION SUP HIGH CAL The SUP HIGH CAL menu items display the currently measured supply flow rate and the calibrated value for that supply flow. The supply dampers move to the SP HIGH SETP damper position for the high calibration. The calibrated supply flow can be adjusted using the / keys to make it match a reference measurement. Pressing the SELECT key saves the new calibration data. FLOW STATION TYPE FLO STA TYPE The FLO STA TYPE item is used to select the flow station input signal. PRESSURE is selected when TSI flow stations with pressure transducers are installed. LINEAR is selected when a linear output flow station is installed. Typically a thermal anemometer based flow station. PRESSURE or LINEAR PRESSURE MAXIMUM FLOW STATION VELOCITY TOP VELOCITY The TOP VELOCITY item is used to input the maximum velocity of a linear flow station output. A TOP VELOCITY must be input for the linear flow station to operate. 0 to 5,000 FT/MIN (0 to 25.4 m/s) 0 NOTE: This item is disabled if a pressure based flow station is installed. Part Two