40
SUPPLY FLOW MENU (continued)
MENU ITEM
SUPPLY FLOW
LOW
CALIBRATION
SOFTWARE
NAME
SUP LOW
CAL
ITEM DESCRIPTION
The SUP LOW CAL menu items display the currently
measured supply flow rate and the calibrated value for
that supply flow. The supply dampers move to the SUP
LOW SETP damper position for the low calibration. The
calibrated supply flow can be adjusted using the /
keys to make it match a reference measurement.
Pressing the SELECT key saves the new calibration
data.
ITEM RANGE
DEFAULT
VALUE
SUPPLY FLOW
HIGH
CALIBRATION
SUP HIGH
CAL
The SUP HIGH CAL menu items display the currently
measured supply flow rate and the calibrated value for
that supply flow. The supply dampers move to the SP
HIGH SETP damper position for the high calibration. The
calibrated supply flow can be adjusted using the /
keys to make it match a reference measurement.
Pressing the SELECT key saves the new calibration
data.
FLOW STATION
TYPE
FLO STA
TYPE
The FLO STA TYPE item is used to select the flow station
input signal. PRESSURE is selected when TSI flow
stations with pressure transducers are installed. LINEAR
is selected when a linear output flow station is installed.
Typically a thermal anemometer based flow station.
PRESSURE or
LINEAR
PRESSURE
MAXIMUM
FLOW STATION
VELOCITY
TOP
VELOCITY
The TOP VELOCITY item is used to input the maximum
velocity of a linear flow station output. A TOP VELOCITY
must be input for the linear flow station to operate.
0 to 5,000 FT/MIN
(0 to 25.4 m/s)
0
NOTE: This item is disabled if a pressure based flow
station is installed.
Part Two