ELECTRIC SERVICE RULES
GENERATION
Issued Jan of 2015
505 . CONNECTION AND NEUTRAL SWITCHING REQUIREMENTS. Figure SEPERATELY DERIVED SYSTEM TRANSFER SWITCH LOCATION 1 Transfer Switch is installed on a feeder with separate equipment grounding and neutral conductors or on a branch circuit. The generator’s neutral is NOT bonded to the generator’s equipment grounding conductor at the generator and a grounding electrode system is NOT required at the generator. 1.
1.
2.
2 3 4 NON‐SEPERATELY DERIVED SYSTEM STANDBY GENERATORS STANDBY GENERATORS * (includes portable generators) The generator’s neutral is bonded to the generator’s equipment grounding conductor at the generator and a grounding electrode system is required at the generator. Connect the generator’s equipment grounding conductor to the feeder’s/branch circuit’s equipment grounding conductor and the generator’s neutral conductor to the feeder’s/branch circuit’s neutral conductor. Neutral must be switched. 2.
Connect the generator’s equipment grounding conductor to the feeder’s/branch circuit’s equipment grounding conductor and the generators neutral conductor to the feeder’s/branch circuit’s neutral conductor. Do not switch the neutral. Transfer Switch on the source side of a single family residential service entrance rated 200 amps or less 1.
(available fault current of 10,000 amps or less). 2.
NEC 547 – Agricultural Building pole top site‐isolating device (transfer switch) 1.
Service entrance rated transfer switch. 2.
Connect the generator’s equipment grounding conductor and neutral conductor to the service entrance’s grounded neutral bus. Do not switch the neutral. Transfer Switch is located on a feeder with a grounded neutral (Allowed prior to 2008 NEC). Connect the generator’s equipment grounding conductor and neutral conductor to systems grounded neutral conductor. Do not switch the neutral. 1.
2.
Connect the generator’s equipment grounding conductor and neutral conductor to systems grounded neutral conductor. Do not switch the neutral. *A separately derived generator is a generator that can be operated without being interconnected to a service entrance panel by a transfer switch. A typical application is to provide power to portable equipment. A non‐separately derived generator can NOT provide power directly to portable equipment. Switching criteria: Do not switch the equipment grounding conductor or the grounded neutral conductor. Do not re‐ground the neutral after the grounded neutral conductor has been separated into a neutral conductor and an equipment grounding conductor..