SiE 00-07 Troubleshooting 3.29 Malfunction of Transmission Between Outdoor Units Remote Controller Display Supposed Causes U7 Improper connection of transmission wiring between outdoor unit and outdoor unit outside control adaptor Improper cool/heat selection Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit) Defect of outdoor unit PC board (A1P) Defect of outdoor unit outside control adaptor Troubleshooting C/H SELECT is set to "IND". YES NO Cool / heat selection is unified. Is the indoor / outdoor unit transmission wiring normal? NO YES Fix the indoor/outdoor unit transmission wiring. Replace the outdoor unit PC Board (A1P). NO Set C/H SELECT to "IND." YES C/H SELECT is set to "MASTER." YES The cool / heat unified address for outdoor units in outdoor - outdoor unit transmission is duplicated. Set the address correctly. NO C/H SELECT is set to "SLAVE." YES Check and see if the following items are normal. NO Fix the problem. NO Outdoor unit outside control adaptor •Is there continuity? •Does the cool/heat unified address match? Outdoor unit (unified master unit) •Is there continuity? •Does the cool/heat unified address match? YES Does a malfunction occur when the cool / heat selector is set to "IND?" NO Replace the outdoor unit outside control adaptor. replacement YES Replace the outdoor unit PC board (A1P). (VF056) Troubleshooting R-407C PLUS Series 151